Programming Operation of SSB-6113
There are 3 types of Set Menu Mode:
Mode 1 is for selection of 12V or 24V when the unit is first activated.
Mode 2 is for adjusting the threshold values of voltages and the related delay time.
Mode 3 is to confirm change of system state such as normal open/ close, ignition control and return to default factory setting.
Unit will automatically exit with the new settings or return to the last set values after 10 seconds for mode 1 and 20 seconds for
mode 2 and 3.
First activate the unit by connecting Main Terminal
to Positive and Neg.
to Negative of a 12V battery for 12V system and
24V battery for 24V system.
4.1 Set Menu Mode 1 ------ Setting of 12V or 24 V system
Press the
/
button to toggle 12V or 24V shown on Display.
Confirm your selection by pressing the
button for 12V system to
button for 24V system for a few seconds.
Display will show the
software version
to confirm setting then the battery voltage.
If no selection is done within 10sec., unit will go back to last set system voltage.
Remark: You have about 10 seconds to confirm your setting otherwise the SSB-6113 will go to the last set system voltage or
factory default setting.
4.2 Set Menu Mode 2 ------ Viewing the Connect Voltage/ Isolate Voltage/ Alert Voltage/ Delay Time
This is the most used Set Menu Mode.
You have to pair the top led “VOLT”, “SEC” with the bottom led “connect”, “isolate” & “alert” to interpret the reading on the
Display as shown in the following diagrams.
To enter into this mode Press both
and
button simultaneously until display shows
then the factory default
Connect Voltage.
You can review the last set values of Connect, Isolate, Alert Voltages, Delay Times and etc.
by toggle the
(forward) or
( back) buttons and take note the pair of lit up LEDs
Connect Voltage (Default 13.7V for 12V system)
Connect Delay Time (Default 5sec)
Isolate Voltage (Default 12.8V for 12V system)
Isolate Delay Time (Default 5sec)
Alert Voltage (Default 12.0V for 12V system)
Alert Delay Time (Default 10sec)