4. 

Programming Operation of SSB-6113 

 
There are 3 types of Set Menu Mode: 
Mode 1 is for selection of 12V or 24V when the unit is first activated. 
Mode 2 is for adjusting the threshold values of voltages and the related delay time.   
Mode 3 is to confirm change of system state such as normal open/ close, ignition control and return to default factory setting. 
Unit will automatically exit with the new settings or return to the last set values after 10 seconds for mode 1 and 20 seconds for 
mode 2 and 3. 
First activate the unit by connecting Main Terminal 

 to Positive and Neg. 

 to Negative of a 12V battery for 12V system and 

24V battery for 24V system.   
 

4.1  Set Menu Mode 1 ------ Setting of 12V or 24 V system

 

 

Press the 

  / 

  button to toggle 12V or 24V shown on Display. 

 

Confirm your selection by pressing the 

  button for 12V system to 

  button for 24V system for a few seconds. 

 
Display will show the 

software version

 to confirm setting then the battery voltage. 

If no selection is done within 10sec., unit will go back to last set system voltage. 
Remark: You have about 10 seconds to confirm  your setting otherwise the SSB-6113  will go to the last set system voltage or 
factory default setting. 
 

4.2  Set Menu Mode 2 ------ Viewing the Connect Voltage/ Isolate Voltage/ Alert Voltage/ Delay Time   
 

This is the most used Set Menu Mode. 
You have to  pair the top led “VOLT”, “SEC” with the bottom led “connect”, “isolate” & “alert” to interpret the reading on the 
Display as shown in the following diagrams. 

To enter into this mode Press both 

  and 

  button simultaneously until display shows 

  then the factory default 

Connect Voltage. 
 
You can review the last set values of Connect, Isolate, Alert Voltages, Delay Times and etc. 

by toggle the 

  (forward) or 

  ( back) buttons and take note the pair of lit up LEDs 

 

Connect Voltage (Default 13.7V for 12V system)   

 

 

Connect Delay Time (Default 5sec) 

 

 

Isolate Voltage   (Default 12.8V for 12V system)   

 

 

Isolate Delay Time (Default 5sec) 

 

 
Alert Voltage (Default 12.0V for 12V system) 

 

 

 

Alert Delay Time (Default 10sec) 

 

 
 
 
 
 

Summary of Contents for SSB-6113

Page 1: ...te sparks near battery or protector during normal operation as batteries may give out explosive gas Do not use the protector if it has been dropped or damaged Do not remove casing of the protector the...

Page 2: ...nitoring finer tuning of voltage delay timer set points and more fail safe protection with diagnostic display 2 Advanced Features Alert Voltage The additional Alert Voltage setting is to monitor the m...

Page 3: ...are version to confirm setting then the battery voltage If no selection is done within 10sec unit will go back to last set system voltage Remark You have about 10 seconds to confirm your setting other...

Page 4: ...Set Mode 2 automatically after 20 seconds with the new settings N O N C Application MODE Normally Open This is the factory default mode The two terminals are normally isolated disconnected open when t...

Page 5: ...protection will lock up the unit until complete reset by disconnect and reconnect the battery Over Temperature Protection Unit Over Temperature 90 C Check location of unit is well ventilated Check cab...

Page 6: ...he spot which is powered up when the Ignition switch is on A External Alert Alarm port An external signal voltage to indicate the operation status of the unit It synchronizes with the Alert Voltage an...

Page 7: ...above control port Neg A R Black wire to Neg Negative ground Red wire to Main terminal Remote Override function Green wire to R Remote Override function Yellow wire to A LED indicator Remark If no int...

Page 8: ...n battery to Aux battery 130mV Protections System Under Voltage Disconnect Auto reconnect when condition returns to normal System Over Voltage Disconnect Auto reconnect when condition returns to norma...

Reviews: