6-12
Planning the electrical connections
DKR Drive Controllers
DOK-DIAX03-DKR********-PR02-EN-P
Isolating transformers
CAUTION
Damage to the isolating transformer if it is not
sized large enough!
⇒
Please note the following guidelines.
⇒
Dimension the power S
Netz
of a possibly isolating transformer in terms
of the rated motor power or at least, however, in terms of the actual
continuous motor power (calculation: see Fig. 6-11).
⇒
Make sure that the power of the isolating transformer, as dependent
upon the drive, does not drop below the values listed in the following
table.:
Type of drive controller
Minimum power of the isolating
transformer (S
Netz
) [kVA]
DKR03.1-100-...
25
DKR03.1-200-...
40
DKR02.1-200-...
50
DKR02.1-300-...
65
DKR04.1-300-...
80
DKR04.1-400-...
100
Fig. 6-13:
Minimum power of the isolating transformer depending on the drive
controller in use
⇒
Make sure that the inductive components of the relative short-circuit
voltage u
KX
are less than 4 % (calculation: see Fig. 6-12).