Mounting and installation
10.1 Adapting the cooling method
DKR02 and DKR03
Drive controllers of type DKR02 and DKR03 are supplied for "Cooling with
air from inside the cabinet". If a different cooling method is required, then
the drive must be converted before it is mounted into the cabinet.
Conversion to cooling method using air outside of
cabinet
It is necessary to convert the cooling method, if
•
there are two rectangular vents near the controller heatsink in the
mounting panel of the control cabinet
•
the air openings on the top and bottom side of the device to be
replaced are closed with covers (which shows that the device was
being operated with air from outside the cabinet).
Note:
As a matter of principle observe the specifications of the
machine manufacturer or control cabinet maker!
The parts required for the conversion to "Cooling with air from outside the
cabinet" can be found in a plastic bag which is attached to the drive
controller.
The plastic bag contains the following parts:
•
cover
1
•
cover
2
•
gasket for cover 1
•
gasket for cover 2
•
8
screws
M4x12
•
8 gaskets for the screws M4