Suction Line Oil Traps
0 to 20 feet (0 to 6.1 m) Rise:
The ice machine head section
has one oil trap built in which allows for a maximum condenser
rise of 20 feet (6.1 m) without additional traps in the suction line.
21 to 35 feet (6.4 to 10.7 m) Rise:
The suction line requires an
additional Oil Trap (“S” type) to be installed. Install the trap as
close as possible to midpoint between the ice machine head
section and CVD condensing unit. See chart below for kits.
3/4 inch (19.1 mm)
K00166
S1200C
S1470C
S1870C
S2070C
5/8 inch (15.9 mm)
K00172
S600C
S850C
S1000C
Tubing Size
S-Trap Kit
Number
Model