Connect the Line Set
Condensing Unit
³
The condensing unit ships from the factory pressurized with a 50/50
mixture of nitrogen/helium. Bleed off pressure from both suction and
liquid line access ports prior to cutting into refrigeration lines.
³
The compressor oil rapidly absorbs moisture.
Be prepared
to complete
line set installation and start your evacuation process in order to
minimize the time the compressor is exposed to the atmosphere.
(Maximum amount of time the system can be exposed to the
atmosphere is 15 minutes). The line set can be routed for entry through
the front or left side of the condensing unit.
³
Remove knockout for preferred location.
³
Insert supplied plastic bushings in knockout holes to prevent tubing
from contacting sheet metal.
³
Use the supplied 90° elbows to route tubing.
³
Cut the tubing ends of the suction and liquid lines and braze the
line sets to the condensing unit.
Summary of Contents for S model
Page 1: ...S Model QuietQube Ice Machines with CVD Technology Installation Training ...
Page 3: ...Typical QuietQube System Installation ...
Page 16: ...Inspection Remove carton inspect ice machine and condensing unit for shipping damage ...
Page 19: ...Model Serial Number Location Back of Ice Machine Inside of Ice Machine ...
Page 21: ...Warranty Registration Website Warranty Registration Form ...
Page 24: ...Ice Machine Wiring Install strain relief and proper wiring to ice machine head section ...
Page 29: ...Potable Water Supply Water Installation without filter Install union and shut off valve ...
Page 32: ...Lift Unit Trained qualified personnel are required for rigging and lifting ...
Page 41: ...Secure Line Set Secure Line Set as Needed Do not crush compress insulation ...
Page 49: ...Final Set Up ...
Page 52: ...S Model QuietQube Ice Machines with CVD Technology Installation Quiz Click Here to Launch ...