110
Part Number STH042 3/14
4. Recovered refrigerant must come from a
“contaminant-free” system. To decide whether the
system is contaminant free, consider:
•
Type(s) of previous failure(s)
•
Whether the system was cleaned, evacuated
and recharged properly following failure(s)
•
Whether the system has been contaminated
by this failure
•
Compressor motor burnouts and improper past
service prevent refrigerant re-use.
•
Refer to “System Contamination Cleanup” on
page 114 to test for contamination.
5. “Substitute” or “Alternative” Refrigerant
•
Must use only Manitowoc-approved alternative
refrigerants.
•
Must follow Manitowoc-published conversion
procedures.