Analyzing Suction Pressure
The suction pressure gradually drops throughout the
freeze cycle. The actual suction pressure (and drop rate)
changes as the air and water temperature entering the
ice machine changes. These variables also determine the
freeze cycle times.
To analyze and identify the proper suction pressure drop
throughout the freeze cycle, compare the published
suction pressure to the published freeze cycle time.
NOTE: Analyze discharge pressure before analyzing
suction pressure. High or low discharge pressure may be
causing high or low suction pressure.
1. Determine the ice machine operating conditions:
Air temp. entering condenser
______
Air temp. around ice machine
______
Water temp. entering sump trough
______
2. Refer to Operating Pressure table (starting on page
223) for ice machine being checked.
Use the operating conditions determined in step 1 to
find the published normal discharge pressures.
Freeze Cycle ______
Harvest Cycle ______
3. Perform an actual suction pressure check.
Freeze Cycle
psig (kPa)
1 Minute into the
Freeze Cycle
__________
Middle of Freeze Cycle
__________
End of Freeze Cycle
__________
4. Compare the actual suction pressure (step 3) with
the published suction pressure (step 2).
NOTE: The suction pressure is normal when the
actual pressure falls within the published pressure
range for the ice machine’s operating conditions.
It is normal for the suction pressure to be higher
at the beginning of the Freeze cycle (when load is
greatest), then drop throughout the Freeze cycle.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......