161
Refer to Symptom #2
Freeze Cycle Operational
Analysis Table
Refer to Heavily Scaled
Cleaning Procedure
Discharge line temperature is greater than
15
0ºF at the end of the freeze cycle
?
Refer to Manual
Cleaning Procedure
Is the evaporator dirty?
(Dry evaporator first then check)
YES
YE
S
NO
NO
NO