141
One Evaporator, Two TXV 48” Models
Tubing routing for one evaporator with two TXV’s is
different. The evaporator has two inlets and outlets. Fill
pattern varies depending on which circuit is affected,
Extremely Thin at the Evaporator Outlet will first be
visible 1/3 of the way down the evaporator. Only one side
of the evaporator may be affected depending on failure.
A TXV failure will usually show on only one side, while low
on refrigerant can affect one or both sides depending on
the amount of refrigerant loss and ambient temperature.
Extremely Thin at the Evaporator Inlet will show at
the bottom of the evaporator. Depending on the failure
either the entire bottom of the evaporator or one side of
the bottom of the evaporator may be affected.
Thin at Inlet
Thin at Outlet
ICE
ICE
ICE
Outlet
Inlet
Outlet
Inlet
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......