186
Symptom #2 Machine is running and the display has a
flashing alert triangle and indicates “HPC Fault” after
the left arrow is pressed
1. Navigate to the event log on the Service menu. Scroll
down to HPC Fault EO5. Open the event and view
when and how often HPCO Fault has occurred.
2. If this is a one time event it may be intermittent and
caused by conditions around the unit changing. For
example: High ambient temperature, water turned
off to condenser (water cooled unit) etc.
3. Run the system to see if the control trips at the rated
pressure. If HPCO opens at a pressure significantly
lower than the control setting of 450 psig replace the
HPCO.
4. If the control opens at the correct pressure (+-10
lbs) find the root cause - Fan motor, dirty condenser,
refrigeration system issue, etc.
Summary of Contents for Indigo ID0302A
Page 2: ......
Page 20: ...20 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...36 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 162: ...162 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 212: ...212 Part Number STH025 11 16 ACCESS REMOTE RECOVERY EVACUATION CONNECTIONS ...
Page 224: ...224 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 266: ...266 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 269: ...Part Number STH025 11 16 269 I0320 1PH AIR WATER Self Contained Air Water cooled ...
Page 270: ...270 Part Number STH025 11 16 I0500 1PH REMOTE Remote Air cooled 000007405_06 ...
Page 277: ...Part Number STH025 11 16 277 I1400 II1406 1800 1PH REMOTE Remote Condenser 000008864_04 ...
Page 278: ...278 Part Number STH025 11 16 I1400 I1406 I1800 3PH REMOTE Remote Condenser 000008864_04 ...
Page 288: ...288 Part Number STH025 11 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 289: ...Part Number STH025 11 16 289 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 290: ......
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ......