background image

3

Smoke extract dampers - multi are shutters in the smoke exhaust piping systems. The dampers are 
designed  to  remove  heat  and  combustible  products  (e.g.  smoke)  from  fire  compartments.  The 
damper blade is controlled by actuating mechanism.  The dampers are designed for using in fire 
compartments that can be connected to the smoke exhaust ducts (tested according to EN 1366-8) 
or they can be installed in or on the construction of the fire compartment.

Dampers are classified according to EN 13501-4.

General information

Classification of Dampers

Supporting 
Construction

Classification

Horizontal duct system

EI 120 (h

od 

- i   o) S1000C

10000

HOT 400/30Mamulti

EI 120 (h

od 

- i   o) S1000C

10000

HOT 400/30AAmulti

Porous concrete ceiling 
construction, 
thickness 150 mm

EI 90 (h

ow 

- i   o) S1000C

10000

HOT 400/30AAmulti

Porous concrete wall 
construction,
thickness 100 mm

EI 120 (v

ew 

- i   o) S1000C

10000

HOT 400/30AAmulti

Gypsum wall, thickness 
100 mm

EI 120 (v

ew 

- i   o) S1000C

10000

HOT 400/30AAmulti

Vertical duct system

EI 120 (v

ed 

- i   o) S1000C

10000

HOT 400/30MAmulti

EI 120 (v

ed 

- i   o) S1000C

10000

HOT 400/30AAmulti

Assembly information

1. During installation the damper blade must be in position “CLOSED”.  The damper body should 

not be deformed in the course of bricking in. Once the damper built in, its blade should not grind 
on the damper body during opening or closing.

3.  During installation the control mechanism must be protect against damaged and pollution.

2. The installation of more dampers into the fire separating construction must meet the following 

requirements:

  - the minimum distance between two dampers has to be 200 mm;
  - the minimum distance between damper and construction (ceiling / wall) has to be 75 mm;

In the event of fire the Smoke and Fire Ventilation System opens the damper in the affected section 
which removes combustion products and heat from this section.

Fire  dampers  are  suitable  for  installation  in  arbitrary  position  (axle  of  the  blade  as  horizontal  or 
vertical). The Air  Flow  (smoke) must be directed  from the control  device side  (see arrow on the 
damper body).

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3 zm.A2.

Summary of Contents for SEDM

Page 1: ...027 12 VALID FROM 01 10 2013 INSTALLATION INSTRUCTIONS MULTI COMPARTMENT SMOKE EXTRACTION DAMPER SEDM...

Page 2: ...neral information 3 Assembly information 3 Installation opening 4 Statement of installation 4 The Blades Overlaps 8 The Flanges 9 Connection Diagrams 9 Service assembly and revisions 11 Dimensions 11...

Page 3: ...al duct system EI 120 ved i o S1000C10000HOT 400 30MAmulti EI 120 ved i o S1000C10000HOT 400 30AAmulti Assembly information 1 During installation the damper blade must be in position CLOSED The damper...

Page 4: ...ceiling construction of fire compartment Installation in the solid wall construction of fire compartment Damper blade is in horizontal position Installation in the solid wall construction of fire com...

Page 5: ...NOTICE The actuating mechanism cover must be removable after installation Installation in the gypsum wall construction of fire compartment Position 1 Damper SEDM 2 Gypsum construction 3 Mineral stone...

Page 6: ...amic paper 4 Hinges 2 4 1 3 Installation on the solid wall construction of fire compartment Damper blade is in horizontal position Installation on the solid wall construction of fire compartment Dampe...

Page 7: ...on 4 5 1 2 3 Pozice 1 Damper SEDM 2 Solid ceiling construction 3 Ceramic paper 4 Hinges 5 Cement lime plate Installation on the solid ceiling construction of fire compartment mounting from top 1 4 2 3...

Page 8: ...air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded Installation in smoke exhaust ducts Installation in vertical...

Page 9: ...0 104 54 Ax560 109 59 Ax600 129 79 Ax630 144 94 Ax650 154 104 Ax700 11 179 129 Ax710 16 184 134 Ax750 36 204 154 Ax800 61 229 11 179 Ax900 111 279 61 229 Ax1000 161 329 111 279 NOTICE The blade of dam...

Page 10: ...10 Actuating mechanism BELIMO BE 230 12 Actuating mechanism BELIMO BE 24 12 ST Actuating mechanism BELIMO BLE 230...

Page 11: ...bserved during fire damper assembly 3 Before entering the dampers into operation after assembly and after sequential revisions checks and functionality tests of all designs including operation of the...

Page 12: ...DM with flanges NOTICE Dimensions for damper with actuating mechanism InMax 50 75 MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 Fax 420 311 584 810 311 584 382 e mail mandik...

Reviews: