background image

11

5.  The adjustment of the blade can be done by connecting the power supply to the actuator (or by 

the signal from the Smoke and Fire Ventilation system). The blade is adjusted to the position 
"OPENED" and then back to position "CLOSED".

6.   Manual operation
 

Any position of the damper blade can be manually set by using a special key. The functionality 
of the damper can be then easily tested.

1. 

 

Assembly,  maintenance  and  damper  check  can  be  done  only  by  qualified  persons,  i.e. 
“AUTHORIZED PERSONS” that have been trained by the manufacturer. 

2.   All effective safety standards and directives must be observed during fire damper assembly.

3.   Before  entering  the  dampers  into  operation  after  assembly  and  after  sequential  revisions, 

checks and functionality tests of all designs including operation of the electrical components 
must  be  done.  After  entering  into  operation,  these  revisions  must  be  done  according  to 
requirement set by national regulations. 

Assembly, service and  revisions

 

Visual inspection of proper fire damper integration, inside fire damper area, fire damper blade, 
contact surfaces and silicon sealing.

4.  After fire damper assembly the following checks must be carried out:

 

Inspection  hole  disassembly:  release  the  covering  lid  by  removing  the  four  screws  in  the 
corners of the inspection hole. Then remove lid from its original position.

Actuating mechanism  SCHISCHEK InMax 50.75-S

Summary of Contents for SEDM

Page 1: ...027 12 VALID FROM 01 10 2013 INSTALLATION INSTRUCTIONS MULTI COMPARTMENT SMOKE EXTRACTION DAMPER SEDM...

Page 2: ...neral information 3 Assembly information 3 Installation opening 4 Statement of installation 4 The Blades Overlaps 8 The Flanges 9 Connection Diagrams 9 Service assembly and revisions 11 Dimensions 11...

Page 3: ...al duct system EI 120 ved i o S1000C10000HOT 400 30MAmulti EI 120 ved i o S1000C10000HOT 400 30AAmulti Assembly information 1 During installation the damper blade must be in position CLOSED The damper...

Page 4: ...ceiling construction of fire compartment Installation in the solid wall construction of fire compartment Damper blade is in horizontal position Installation in the solid wall construction of fire com...

Page 5: ...NOTICE The actuating mechanism cover must be removable after installation Installation in the gypsum wall construction of fire compartment Position 1 Damper SEDM 2 Gypsum construction 3 Mineral stone...

Page 6: ...amic paper 4 Hinges 2 4 1 3 Installation on the solid wall construction of fire compartment Damper blade is in horizontal position Installation on the solid wall construction of fire compartment Dampe...

Page 7: ...on 4 5 1 2 3 Pozice 1 Damper SEDM 2 Solid ceiling construction 3 Ceramic paper 4 Hinges 5 Cement lime plate Installation on the solid ceiling construction of fire compartment mounting from top 1 4 2 3...

Page 8: ...air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded Installation in smoke exhaust ducts Installation in vertical...

Page 9: ...0 104 54 Ax560 109 59 Ax600 129 79 Ax630 144 94 Ax650 154 104 Ax700 11 179 129 Ax710 16 184 134 Ax750 36 204 154 Ax800 61 229 11 179 Ax900 111 279 61 229 Ax1000 161 329 111 279 NOTICE The blade of dam...

Page 10: ...10 Actuating mechanism BELIMO BE 230 12 Actuating mechanism BELIMO BE 24 12 ST Actuating mechanism BELIMO BLE 230...

Page 11: ...bserved during fire damper assembly 3 Before entering the dampers into operation after assembly and after sequential revisions checks and functionality tests of all designs including operation of the...

Page 12: ...DM with flanges NOTICE Dimensions for damper with actuating mechanism InMax 50 75 MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 Fax 420 311 584 810 311 584 382 e mail mandik...

Reviews: