Page 29
Version 2022-12-20
MSD - multi smoke damper
TPM 159/22
■
The dampers must be suspended using threaded rods and
mounting profiles. Their dimensioning depends on the
damper's weight.
■
The dampers and duct must be suspended separately.
■
The connected duct must be suspended in such a way that
the transfer of all loads from the adjoining ventilation duct
to the damper body is completely excluded. Adjacent duct
must be suspended or supported, as required by the duct
suppliers.
■
Threaded rods longer than 1,5 m must be protected by
fire insulation.
With hinge plate and anchors
Screw with internal
thread and hexagon drive
Without anchor
With anchor
Possible examples of anchoring to the ceiling construction
Follow the instructions of fixing specialist or installation company
Hinge plates
2x
Ø
9
M8 t
o M
16
120
80
5
0
4x
Ø
9
M20
100
150
■
If in doubt then always consult a specialist
anchor engineer such as Halfen or Hilti.
1
Threaded rod M8 - M20
2
Nut M8 - M20
3
Washer for M8 - M20
4
Coupling Nut M8 - M20
5
Anchor
6
Hinge plate - min. thickness 10 mm
7
Concrete screw tested for fire resistance R30-R90,
max. Tension up to 0.75 KN (length 35 mm)
Load capacities of threaded hanger rods F [N] at
the required fire resistance 90 minutes
Size
As [mm²]
Weight G [kg]
for 1 piece
for 1 pair
M8
366
22
44
M10
58
35
70
M12
843
52
104
M14
115
70
140
M16
157
96
192
M18
192
117
234
M20
245
150
300
Mounting to the ceiling wall