8
Day of the
week
1
06:00
Time
setting
20°C
Temperature
setting
2
08:00
15°C
3
11:30
15°C
4
12:30
15°C
5
17:30
22°C
6
22:00
15°C
Weekend
1
08:00
22°C
2
22:00
15°C
V
V
V
V
This setting can be entered when the device is switched off by holding down the button and . The
setting is done according to the following table 5.1. Use the button to jump between settings. Leave the
setting by pressing .
1
ADJ
Temperature calibration
0
Adjust temperature range: -5 to +5°C
2
CTL
Fan control option
0
Uncontrol: 0 control: 1
3
OLT
Output voltage limit
10
Adjust range: 5-10V
4
AdH
Communication address high
0
0x00-0xff
5
AdL
Communication address low
1
0x00-0xff
6
LTP
Low temperature protection
0
0: off 1: on
7
SEN
Sensor mode
0
0: built-in sensor
1: external sensor
8
FAC
Reset to factory seting
8
Reset by setting the value to 0
V
V
1)
To enter the weekly program, press and hold the button
2)
Instead of time the inscription LOOP appears on the screen, use the to select the week format
a) If we set the number 5, we will heat 5 days a week according to the set program and the temperature
for weekend will be set separately. The format of the week is 5 + 2
b) If we set the number 6, we will heat 6 days a week according to the set program and set the
temperatures for Sunday will be set separately. The format of the week is 6 + 1
c) If we set the number 7, all the days of the week will be heated the same way. The format of the week
is 7.
3)
Day of the week can be divided into 6 events (6 sections with different temperatures), if you set the
format of the week to 6 + 1 or 7, the weekend is divided into 2 events. After selecting the week format,
use the button to switch between the individual time periods and the button to switch between
the temperature and time settings.
4)
The settings is made according to the following table 4.1. Temperature and time values are preset.
V
V