1 Inner tube (plug in throat)
2 Outer tube with throat
3 Strap M12
4 Tenon
5 Bowl buckle
6 Wascher 13
7 Nut M12
●
Burner box
●
Exhaust (ventilation) box
●
Connecting cable with connector
●
Radiant pipes
●
Pipe connections, arch
●
Hinges with fixing straps
●
Reflectors
●
Connecting material
●
Remote control box, connecting cables
●
Accessories, auxiliary fastening and connecting material
●
Venting or combustion air inlet pipeline
Before starting installation, make sure that local condition regarding gas line, fuel and its pressure and
heater setting are compatible.
Installation of the heater must be carried out in such way so that an adequate space for servicing and
adjustment is maintained (Fig. 9, 10). There must be ensured sufficient air exchange in the building to
allow for good combustion of gas. The amount of combustion air for the infrared heaters must meet
applicable standards. For installation of heaters in dusty environment, installation of duct supplying the
combustion air from outside (Closed appliance) is strongly recommended. The installation must comply
with applicable standards and regulations and with this installation manual.
Infrared heaters cannot be installed in places where there is a risk of fire or explosion or high levels of
flammable dust.
Infrared heaters HELIOS can be used for heating in public areas where this type of heating is permitted
by legislation. It is necessary to comply with the regulations for installation in these areas.
Connect the radiant pipes and with U and LU shaped heaters the arch by pushing into the sockets
up to the bottom according to the respective assembly diagram. Before joining the arch to the pipes,
first place the hinge with pate. Every time before joining new piece of radiant tube, put the hinges
according to the assembly diagram of the respective heater on the assembled part of the heater. The
hinges cannot be pulled over the installed socked pipe connection with clamp. Only after the hinges
are put on place, lock the socked pipe connection with clamp. The clamps have to be tightened
firmly, recommended torque is 20 Nm. – the connection has to be firm and tight.