Fire damper - FDMR
TPM 140/19
■
The method of attachment must
follow the minimum require-
ments for attachment and con-
nection
of
ductwork
in
accordance with national regula-
tions. Also, the elements can be
suspended from the top, or sup-
ported from bottom, or fastened
from the side.
Example of fixing FDMR outside the wall or ceiling
Outside solid wall construction
Outside solid ceiling construcion
Outside gypsum wall construction
Ø100–400
t(mm): 1,5
Ød
t
2
0
Ø450–800
t(mm): 2,5
Ød
t
2
5
A
B
A
B
A
B
9
Nut M8 with anchor
10
Hexagon head screw
11
Gypsum grid from “U” profile
12
Fixing element/steel bracket for fixing the duct to
the wall or ceiling (optional accessory MANDÍK, a.s.)
13
Mounting holes for rivets
14
Duct insulation
Ø100–400
Quick closing system
2x screw M6×20.
Fixing nut for threaded rod M8.
Ø450–800
2x screw connection M10x30 or threaded rods M10
Combined fixing nut for threaded rod M8+M10.
1
Solid wall construction
2
Solid ceiling construction
3
Gypsum wall construciton
4
FDMR
5
Duct
6
Filling of space between the damper and
wall/ceiling
7
Circular suspension with threaded rod
8
Mouting brackets (according to order) -
determine min. length of the insulation (built in
edge). Bend the mounting brackets 90 degrees
from a damper casing. If the insulation is longer
than the mounting bracket position, break off
the brackets.