Page 27
Version 2023-06-15
Fire damper - FDMR
TPM 140/19
Statement of installations
Installation
wall/ceiling
min. thickness
[mm]
Method of installation
Fire resistance
Page
In solid wall construction
100
Mortar or gypsum
EI 90 (v
e
i
↔
o) S
EI 120 (v
e
i
↔
o) S
2 dampers in one opening - mortar or gypsum
EI 90 (v
e
i
↔
o) S
Weichschott system
Mineral wool with fire-resistant coating and fire-resistant boards
Fire-resistant foam with stucco plaster
EI 60 (v
e
i
↔
o) S
Installation next to the wall/ceiling - mortar or mineral wool
EI 90 (v
e
i
↔
o) S
Installation next to the wall/ceiling - mortar or gypsum
Outside solid wall construction
100
ISOVER Ultimate Protect - mortar or gypsum
EI 60 (v
e
i
↔
o) S
EI 90 (v
e
i
↔
o) S
ISOVER Ultimate Protect - Weichschott system
Mineral wool ROCKWOOL - Mineral wool with fire-resistant coating and fire-
resistant board
EI 90 (v
e
i
↔
o) S
In gypsum wall construction
100
Mortar or gypsum
EI 90 (v
e
i
↔
o) S
EI 120 (v
e
i
↔
o) S
2 dampers in one opening - mortar or gypsum
EI 90 (v
e
i
↔
o) S
Weichschott system
Weichschott system - wooden construction (wooden beams)
Mineral wool with fire-resistant coating and fire-resistant boards
Fire-resistant foam with stucco plaster
EI 60 (v
e
i
↔
o) S
Installation next to the wall/ceiling - mortar or mineral wool
EI 90 (v
e
i
↔
o) S
Installation next to the wall/ceiling - mortar or gypsum
Outside gypsum wall construction
100
ISOVER Ultimate Protect - mortar or gypsum
EI 60 (v
e
i
↔
o) S
EI 90 (v
e
i
↔
o) S
ISOVER Ultimate Protect - Weichschott system
Mineral wool ROCKWOOL - Mineral wool with fire-resistant coating and fire-
resistant boards
EI 90 (v
e
i
↔
o) S
In sandwich wall construction
100
Weichschott system with fire-resistant boards
EI 90 (v
e
i
↔
o) S
In shaft wall Rigips
110
Mortar or gypsum
EI 90 (v
e
i
↔
o) S
80
Installation frame R1
In solid ceiling construction
110 - Concrete
125 - Aerated
concrete
Mortar or gypsum
EI 90 (h
o
i
↔
o) S
EI 120 (h
o
i
↔
o) S
2 dampers in one opening - mortar or gypsum
EI 90 (h
o
i
↔
o) S
Weichschott system
Mineral wool with fire-resistant coating and fire-resistant boards
Outside solid ceiling construction
110 - Concrete
125 - Aerated
concrete
ISOVER Ultimate Protect - mortar or gypsum (damper under ceiling)
EI 60 (h
o
i
↔
o) S
EI 90 (h
o
i
↔
o) S
ISOVER Ultimate Protect - mortar or gypsum (damper above ceiling)
Mineral wool ROCKWOOL - mortar or gypsum
EI 90 (h
o
i
↔
o) S
Concreting
Installation frame in solid wall
construction
100 (R1), 150 (R2) Installation frame R1, R2
EI 90 (v
e
i↔o) S
100 (R3), 150 (R4) Installation frame R3, R4
100
Installation frame R5
2 dampers in one opening - installation frame R1
100 (R1), 150 (R2) Installation next to the wall/ceiling - installation frame R1, R2
100
Installation next to the wall/ceiling - installation frame R5
Installation frame outside solid
wall construction
100
Insulation from fire-resistant boards - mortar or gypsum - installation frame R6
EI 90 (v
e
i↔o) S
Installation frame in gypsum wall
construction
100 (R1), 150 (R2) Installation frame R1, R2
EI 90 (v
e
i↔o) S
100
Installation frame R5
2 dampers in one opening - installation frame R1
100 (R1), 150 (R2) Installation next to the wall/ceiling - installation frame R1, R2
100
Installation next to the wall/ceiling - installation frame R5
Flexible ceiling - installation frame R7
Installation frame in solid ceiling
construction
110 - Concrete (R1)
150 (R2)
Installation frame R1, R2
EI 90 (h
o
i
↔
o) S
110 - Concrete (R3)
150 (R4)
Installation frame R3, R4
110 - Concrete
125 - Aerated
concrete
Installation frame R5
150
2 dampers in one opening - installation frame R2
Installation frame outside solid
ceiling construction
110 - Concrete
125 - Aerated
concrete
Concreting - installation frame R5
EI 90 (h
o
i
↔
o) S
Insulation from fire-resistant boards - mortar or gypsum - installation frame R6