31
TPM 092/13
17. Quick review
Damper
FDMD
Size
100 - 200
Fire separating construction
Wall/Ceiling
Installation
Fire rezistance
Fig.
Min. thickness [mm]
Solid wall construction
100
Mortar or gypsum
EIS 120
EIS 90
25
100
Stuffing box with fire protection mastic
EIS 90
26
100
Weichschott
EIS 90
27
100
Installation frame D1
EIS 90
34
150
Installation frame D2
EIS 90
34
100
Installation frame D3
EIS 90
35
150
Installation frame D4
EIS 90
35
100
Battery installation
EIS 90
39
Gypsum wall construction
100
Mortar or gypsum
EIS 120
EIS 90
28
100
Stuffing box with fire protection mastic
EIS 90
29
100
Weichschott
EIS 90
30
100
Installation frame D1
EIS 90
34
150
Installation frame D2
EIS 90
34
100
Installation frame D3
EIS 90
35
150
Installation frame D4
EIS 90
35
100
Battery installation
EIS 90
40
Solid ceiling construction
150
Mortar or gypsum
EIS 120
EIS 90
31
150
Stuffing box with fire protection mastic
EIS 90
32
150
Weichschott
EIS 90
33
150
Installation frame D1
EIS 90
34
150
Installation frame D2
EIS 90
34
150
Installation frame D3
EIS 90
35
150
Installation frame D4
EIS 90
35
Outside solid wall
construction
100
Installation frame D6
EIS 90
37
Outside solid ceiling
construction
150
Concrete
EIS 90
38
150
Concrete with installation frame D5
EIS 90
36
150
Installation frame D6
EIS 90
37
An solid wall construction
100
Installation frame D5
EIS 90
36
An solid ceiling construction
150
Installation frame D5
EIS 90
36
Tab. 16.1.1. Quick review