9
TPM 092/13
While a flashing green LED pilot light signalises flap blade motion towards the given position, the
same pilot light reports reaching the required position when shining constantly. If the damper, with
respect to the given time, does not reach the required position, then a red LED pilot light starts to
flash and at the same time, the failure contact is active. Once the damper blade reaches the given
position, this contact is deactivated. The LED pilot light keeps flashing unless the failure is
unblocked by means of the RESET button.
Fig. 13 Komunikační a řídící přístroj BKS 24-1B
Tab. 3.2.1.
Communication and Control Device BKS 24-1B
Communication and Control Device
BKS 24-1B
Nominal voltage
AC 24 V 50/60Hz
Power consumption
2,5 W (operating position)
Dimensioning
5 VA
Protection Class
III (safe small voltage)
Degree of protection
IP 30
Ambient Temperature
0
+ 50 °C
Connection
Into ZSO-11 connector which is not a part of BKS 24-1B.
ZSO-11 connector has screw terminals 11 x 1,5 mm
2
4
BKS24-1B
7
8
2
10
1
5
9
an insulation
transformer
~
AC 24 V
damper position
breakdown
Notice: Relay contacts are drawn
without power
11
b
a
2-conductor wiring
to BKN230-24
Control
on /off
Reset
Test
External buton
optional
be interchanged
6
3
AC
24V
damper position
operation
Reset
Test
open
closed
alarm
failure
Connection through
conection can
Power supply AC 24V
Check test cca 35sec
, starting with switching AC 24 on or pressing
«Reset/Test» button
Current failure,
possible cause: • short circuit or interruption of 2-conductor wiring
or damper failure (at BKN..) • Power supply AC 230V missing • defective
thermoelectrical starting • smoke detector activated • exceeded operation time
Failure saved in memory
• Fault in system signalled, system check should be
done
Damper (drive) turning into
the direction
of breakdown position
Damper (drive) in
breakdown position
Damper (drive) turning into
the direction
of operating position
Damper (drive) in
operating position
Signals and diagnosis
light diodes
contacts
Description
Cause/Course
state
open
closed
alarm
closed
flashing
6
3
6
3
6
7
6
4
6
4
6
3
6
3
6
7
switched
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
closed
open
open
open
open
open
open
flashing
flashing
• damper blocked
not available