15
TPM 092/13
Fig. 27 Installation in a solid wall construction
Position:
1
Fire damper FDMD
2
Fire resistant board
3
Fire stop coating thickness 1 mm
4
Duct
Used materials - example:
2
Hilti CP673 PF
3
Hilti CP673
1
4
2
3
Fig. 26 Installation in a solid wall construction
Position:
1
Fire damper FDMD
2
Stuffing box (mineral stone wool
min. density 140 kg/m ) or
another approved fire sealing
system for damper installation
3
Fire protection mastic Promastop
P,K or equal min. thickness 1 mm
4
Duct
Used materials - example*:
2
Promapyr, Rockwool Steprock HD
3
Promastop - P, K
* Stuffing box and fire protection mastic materials can be replaced by another
approved fire sealing system for damper installation with equivalent
material properties
3
3
2
Min. 50
1
4
Position:
1
Fire damper FDMD
2
Mortar or gypsum with min. density
800 kg/m or another approved fire
sealing system for damper installation
3
Duct
Fig. 25 Installation in a solid wall construction
3
2
3
1
6.2.
Conventional methods of fire dampers installation
EIS 120
EIS 90
EIS 90
EIS 90