30
TPM 075/09
Damper
type
FDMB installation
Classifica
tion
Figure
Square
(max.
dimension
1000x500
or
500x1000,
max. area
0,5m )
Damper installed: in a solid wall construction, min. thickness 100 mm
in a a gypsum wall construction - classification EI 90 in a
solid ceiling construction, min. thickness 150 mm
Installations with using installation frame E1
EIS 90
59
Damper installed: in a solid wall construction, min. thickness 100 mm
in a solid ceiling construction, min. thickness 150 mm
Installations with using installation frame E2
EIS 90
60
Damper installed: in a a gypsum wall construction - classification EI 90
Installations with using installation frame E3
EIS 90
61
Damper installed: on a solid wall construction, min. thickness 100 mm
on a solid ceiling construction, min. thickness 150 mm
outside of solid ceiling construction, min. thickness 150 mm -
installation in conncrete chanell
Installations with using installation frame E4
EIS 90
62
Damper installed: outside of solid wall construction, min. thickness 100 mm
outside of solid ceiling construction, min. thickness 150 mm
Installations with using installation frame E6.
EIS 90
63
Round
(size
160-630)
Damper installed: in a solid wall construction, min. thickness 100 mm
in a a gypsum wall construction - classification EI 90 in a
solid ceiling construction, min. thickness 150 mm
Installations with using installation frame R1 or R2
EIS 90
64
Damper installed: in a solid wall construction, min. thickness 100 mm
in a a gypsum wall construction - classification EI 90 in a
solid ceiling construction, min. thickness 150 mm
Installations with using installation frame R3 or R4
EIS 90
65
Damper installed: on a solid wall construction, min. thickness 100 mm
on a solid ceiling construction, min. thickness 150 mm
outside of solid ceiling construction, min. thickness 150
mm - installation in conncrete chanell
Installations with using installation frame R5
EIS 90
66
Damper installed: outside of solid wall construction, min. thickness 100 mm
outside of solid ceiling construction, min. thickness 150 mm
Installations with using installation frame R6
EIS 90
67
Square and
round
dampers
Installation in a solid wall construction, min. thickness 100 mm, near
the ceiling or wall. Gap is filled by gypsum or mortar and mineral stone wool
EIS 90
68
Installation in a gypsum wall construction, classification EI 90, near the ceiling
or wall. Gap is filled by gypsum or mortar and mineral stone wool
EIS 90
69
Installation in a solid wall construction, min. thickness 100 mm. Installation of
2 fire dampers abreast - gap is filled by gypsum or mortar
EIS 90
70
Installation in a solid wall construction, min. thickness 100 mm. Installation of
2 fire dampers abreast - gap is filled by gypsum or mortar
EIS 90
71
Tab. 6.1.2. Damper installations with using installation frames
NOTICES:
1) Solid wall construction: normal concrete/masonry or porous concrete with minimum thickness
100 mm
2) Solid ceiling construction: normal concrete/masonry or porous concrete with minimum
thickness 150 mm
3) analogical approved fire insulation system = identical thickness, identical , identical reaction
to fire, analogical lambda and c
p
4) Reinforcement of damper VRM-III
2