8
TPM 075/09
Fig. 14 Actuating mechanism BELIMO BF 24-T(-ST), BF 230-T
M
1
2
S3
S1 S2
S5
S4
S6
AC230 V
N L1
BF24-T(-ST), BF230-T
BF230-T: for separation from the mains, a device that
insulates polar conductors must be at disposal
Connection 24V through
an insulation transformer.
DC 24 V
AC 24 V
~
- +
BLF24-ST-T: Design with connector plugs for communication
Parrallel connection of other driver is possible.
Pay attention to the power input data.
<5°
<80°
(Minimum distance between contacts - 3 mm).
to network and communication device BKN230-24
BAE72B-S
Tf1
Tf2
Tf3
LED
Design .41, .51
Design .41 or .51 with actuating mechanism can be complemented with smoke detector MHG
231. The voltage can be AC 230 V or AC/DC 24 V. Design with voltage AC 230 V is equpped with
Communication and supply device BKN 230-24-MA and with actuating mechanism BF 24-T (BLF
24-T).
The smoke detector is activated when smoke spreads in air duct system. Deactivation of smoke
detector is provided by interruption of supply voltage for min. 2s.
Tab. 2.2.3.
Optical smoke detector MHG 231 with the socket MHY 734.031
Optical smoke detector
MHG 231 with socket MHY 734.031
Nominal voltage
AC/DC 24 V
Voltage range
AC 18 … 28 V
DC 24 … 30 V
Power Consumption Socket
(without actuating mechanism)
max. 50mA
Degree of protection
IP 40
Ambient temperature
Non-operating temperature
- 25 °C … + 70 °C
- 5 °C … + 40 °C
Connection - net
- motor
- communication and supply device
BKN 230-24-MA
Cabel 1m, connected to terminal XT1
Screw terminals on the terminal block XT2
Screw terminals on the terminal block XT1 a XT2