TPM 075/09
Tab. 9.2.1. Coefficient of local pressure loss - round dampers
D
160
180
200
225
250
280
315
355
400
450
500
560
630
1,812 1,380 1,110
0,892
0,747
0,627
0,531
0,455
0,393
0,344
0,307
0,273
0,243
10.
Noise data
10.1.
Level of acoustic output corrected with filter A.
L
WA
= L
W1
+ 10 log(S) + K
A
10.2.
Level of acoustic output in octave ranges.
L
Woct
= L
W1
+ 10 log(S) + L
rel
10.3.
Table of acoustics values
L
WA
[dB(A)] level of acoustic output corrected with filter A
L
W1
[dB]
level of acoustic output L
W1
related to the 1 m section (see Tab. 10.3.1. a 10.3.2)
S
[m ]
duct cross section
K
A
[dB]
correction to the weight filter A (viz Tab. 10.3.3.)
2
L
Woct
[dB]
spectrum of acoustic output in octave range
L
W1
[dB]
level of acoustic output L
W1
related to the 1 m section (see Tab. 10.3.1. a 10.3.2)
S
[m ]
duct cross section
L
rel
[dB]
relative level expressing the shape of the spectrum (see Tab. 10.3.3.)
2
2
2
9.2.
Coefficient of local pressure loss (-) - round dampers
Tab. 10.3.1.
Level of acoustic output L
W1
[dB] related to the 1 m section - square dampers
[-]
w [m.s ] 0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
1,5
2
2,5
2
15,5 18,7 20,9 22,6 24,0
25,2
26,3
27,2
28,0
31,2
33,4
35,1
3
26,1 29,2 31,5 33,2 34,6
35,8
36,9
37,8
38,6
41,7
44,0
45,7
4
33,6 36,7 39,0 40,7 42,1
43,3
44,3
45,3
46,1
49,2
51,5
53,2
5
39,4 42,5 44,8 46,5 47,9
49,1
50,2
51,1
51,9
55,0
57,3
59,0
6
44,1 47,3 49,5 51,3 52,7
53,9
54,9
55,8
56,6
59,8
62,0
63,8
7
48,2 51,3 53,5 55,3 56,7
57,9
58,9
59,8
60,7
63,8
66,1
67,8
8
51,6 54,8 57,0 58,8 60,2
61,4
62,4
63,3
64,1
67,3
69,5
71,3
9
54,7 57,9 60,1 61,8 63,2
64,4
65,5
66,4
67,2
70,4
72,6
74,3
10
57,4 60,6 62,8 64,6 66,0
67,2
68,2
69,1
70,0
73,1
75,3
77,1
11
59,9 63,1 65,3 67,1 68,5
69,7
70,7
71,6
72,4
75,6
77,8
79,6
12
62,2 65,4 67,6 69,3 70,7
71,9
73,0
73,9
74,7
77,9
80,1
81,8
2