background image

Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.

Page 1.080

3/16  IOM-FDIMP

OPERATION AND MAINTENANCE PROCEDURES

CURTAIN TYPE FIRE DAMPERS

MODEL SERIES: (D)0100, 0200, 0300 AND (D)0500

Page 1 of 2

Dampers are an essential part of the fire protection system in a building. The NFPA recommends that fire dampers be

tested periodically to verify the operational abilities of each installed damper. See NFPA 80, 

Standard for Fire Doors and

Other Opening Protectives

, for Operational Test and Periodic Inspection and Testing details.

CAUTION:

Some curtain fire dampers utilize high torque springs under tension; ensure HVAC fans are turned off. Testing spring

assisted fire dampers under airflow conditions is 

NOT RECOMMENDED

and may severely damage or destroy ductwork.

Use protective eyewear or safety glasses. Keep hands out of the blade path, as this can cause serious injury. Keep any

hard objects or tools out of the blade path as they can damage the blades when closing.

Periodic Inspection, Testing and Maintenance

Consult  your  local  building  code  to  verify  whether  there  is  a  required  maintenance  and  testing  schedule.  Most  local

jurisdictions reference NFPA 80 for Fire Dampers. Per NFPA 80, each damper should be tested and inspected 1 year after

installation and then every 4 years, except for hospitals, where the frequency is every 6 years.

1. Remove any obstructions, dirt, rust, corrosion, or other observed conditions that could impede proper damper operation.
2. Check closure springs (if applicable). If damaged or defective, repair or replace.
3a. Non-Spring Assisted Dampers

Bend metal straps away from damper frame so that they are straight. Remove

fusible link and allow the blade package to drop and close naturally by the force

of gravity. See Detail 1. Use caution, keeping fingers, hands, arms and tools out

of the blade path.

3b. Dynamic Rated or Spring Assisted Dampers

AS SOON AS THE LINK HAS BEEN REMOVED, THE SPRING WILL FORCE THE

BLADES TO CLOSE INSTANTANEOUSLY. THE BLADE PATH MUST BE KEPT

CLEAR.

4. Ensure the damper closes completely, without assistance. If the damper design

incorporates  a  locking  ramp  to  hold  the  damper  in  the  fully  closed  position,

confirm that the ramp locks properly.

5. Clean damper blades and other moving parts if necessary. Use of a mild detergent or solvents is recommended for

any cleaning required. Lubricate moving parts with a dry lubricant (such as T.F.E. Dry Lube). Never use a regular

lubricating oil on dampers, as it will attract dirt and grit. 

6. Lift the blade package to the top of the damper to reopen and replace the fusible link. Take care not to rack, deform

or damage the blades when reopening.

Reopening  spring  assisted  fire  dampers  may  be  extremely  difficult  and  in  some  cases,  impossible.

If it is determined that the damper is impossible or impractical to test or reopen, a thorough examination of the blade path

is required to ensure that nothing will prevent the damper from closing. Common obstructions include: racked damper

frames, retaining angle installation screws, construction debris and contaminants.

7. Slide the replacement fusible link onto the metal straps. When replacing the fusible link, make sure it is the same

temperature rating of the link you are replacing. If a different temperature, contact factory. Install fusible link so that

the temperature rating is facing outward and is visible.

8. Bend the metal straps up to hold the fusible link in place.

Detail 1

Reviews: