10
11
EN
IMPORTANT: Please read the instruction manual carefully prior to installation and
keep it for future reference.
1. This product should be installed by a registered electrician in accordance with
local standards and electrical regulations.
2. Ensure the mains supply is cut off before installation.
3. Check the unit label for correct supply voltage and frequency.
NOTE
1. The diffuser must not be covered.
2. The rating label must not be removed from the lamp.
3. The fitting must not be link connected (only one connection per fitting).
DESCRIPTION
The fitting is equipped with LED module. Complete with driver. With integrated
emergency light inverter which detects when there is a power failure and switches
to battery power. In emergency light mode the light drops to 260lm/3W. The lu-
minaire is provided with charging indicator/test button. With maintained and non-
maintained operation.
TECHNICAL SPECIfICATIONS
Art.no:
99 750 67
99 750 78
Wattage:
15W
22W
Lumen:
1000lm
1580lm
Dims ØxH:
290x103 mm
350x103 mm
Mounting:
Wall or ceiling.
Note:
The terminal block is located under
the diffuser. Loosen the screw on the diffuser then twist the
diffuser and remove it. Connect the luminaire to the mains.
Connection:
To terminal block 3x2.5 mm²
Protection Class:
IP65
LED Power:
Max. 3W
Lumen LED:
260lm
Input Voltage:
230V, 50Hz
Discharge Duration:
3h
Battery:
NiMH, 7.2V 1.8Ah
Luminaire
Emergency Light