DESCRIPTION
OF THE FUNCTION
SYMBOL
RANGE OF SETTINGS
FACTORY
SETTING
entry in the settings
UC
access code
12.0
limitation of the lower value
for the control temperature
range
1
b1
the possibility of setting the temperature
from -40
O
C to +99
O
C, every 1,0
O
C
2.0 (
O
C)
limitation of the upper value
for the control temperature
range
1
b2
the possibility of setting the temperature
from -40
O
C to +99
O
C, every 1,0
O
C
10.0 (
O
C)
control hysteresis
HI
the possibility of setting the temperature
from 1,0
O
C to 20
O
C, every 0,1
O
C
2.0 (
O
C)
blockade of control
temperature changes
LF
0 – off (blockade inactive)
1 – on (blockade active)
0
delay of turning on cooling for
milking time
0d
0 – off
>0 – on: the possibility of setting the time
from 0 min. to 99 min., every 1 min.
0
milk pre-cooling time
FC
0 – off
>0 – on: the possibility of setting the time
from 0 h to 18 h, every 1 h
0
minimum working time of the
unit
CA
0 – off
>0 – on: the possibility of setting the time
from 0 min. to 60 min., every 1 min.
0
maximum working time of the
unit
2
CC
0 – off
>0 – on: the possibility of setting the time
from 0 h to 9 h, every 1 h
0
minimum standstill time
of the unit
CF
0 – off
>0 – on: the possibility of setting the time
from 0 min. to 60 min., every 1 min.
0
AS
changing the parameter value is not
recommended
3
3.0
AP
3.0
stirrer operating mode
F0
0 – work according to times set in
parameters E1 and E2, independent of the
operation of the unit
1 – continuous work during the unit
operation, and during the standstill of the
unit, the stirrer works according to times
set in parameters E1 and E2
1
standstill time of the stirrer
E1
the possibility of setting the time from 1 min.
to 60 min., every 1 min.
15 (min.)
working time of the stirrer
E2
the possibility of setting the time from 1 min.
to 60 min., every 1 min.
2 (min.)
stirrer manual operation
CP
0 – continuous work
>0 – the possibility of setting the time from 1
min. to 60 min., every 1 min.
5 (min.)
LP
changing the parameter value is not
recommended
3
14.0
EP
40
CL
1
delay in measuring the
maximum and minimum
temperatures after turning on
the cooling process
AA
the possibility of setting the time from 0 h to
18 h, every 1 h
2.0 (h)
return to factory settings
PP
0 – off
0