background image

Strona 

21

 z 

26

 

 

 

 

ATTENTION 
1.  When  programming  the  activation  of  the  hydrostatic  input  (relay  no.  8),  it  is 
necessary  to  program  the  maximum  allowable  time  of  pouring  water.  The  time 
parameter is superior to the hydrostatic signal, providing protection against too much 
water.  Not  programming  this  parameter  will  result  in  the  lack  of  reaction  to  the 
hydrostatic signal and at the same time the lack of pouring water. 
2. Before creating a new program or editing an existing program, it is recommended 
to  create  a  table  as  shown  in  the  description  of  the  programs.  This  will  facilitate 
efficient programming. 
3. In the event of inactivity during programming, the controller automatically exits 
this process without saving changed data. 

 

 

 
 

4.3.3. Returning to the factory (default) settings. 

To return to the default settings, enter the controller settings. Use the 

 and 

 buttons 

to  select  the  Pd0d  parameter,  confirm  the  selection  by  pressing  the  S  button,  then 
change the value of this parameter from 0 to 1 using the 

 button. Then confirm the 

changes by pressing the S button again. After doing this, disconnect the power supply 
from the controller and switch it on again. 
 
 

Summary of Contents for MCH-07 v. 2

Page 1: ...n accidentally to activate the washing process during the cooling process The washing segment is activated only when the cooling is switched off The MCH 07 v 2 controller has a waterproof casing prote...

Page 2: ...ROLLER In order to install the controller unscrew the six screws and swivel the front of the controller paying attention to the cable connecting the upper PCB board with the bottom board After unfoldi...

Page 3: ...n to drill the housing and fix the casing through such holes because it causes loss of tightness of the casing MCH 07T version In the event that the relay no 4 in the washing segment is set as the sti...

Page 4: ...no 5 3 COOLING SEGMENT Activation of the cooling process by the user blocks the possibility of switching on the washing process which results in the total turning off of the washing segment display vi...

Page 5: ...e stirrer 10A 250V AC 3 2 Controller functions in the cooling mode The cooling segment of the MCH 07 v 2 controller is equipped with the functions described below 1 Function that allows controlling th...

Page 6: ...s mode and make the required corrections The following figure illustrates the programming procedure 3 4 Cooling segment operation by the installer Entering the settings can be made both when the cooli...

Page 7: ...aximum working time of the unit2 CC 0 off 0 on the possibility of setting the time from 0 h to 9 h every 1 h 0 minimum standstill time of the unit CF 0 off 0 on the possibility of setting the time fro...

Page 8: ...l diode is permanently on FC 0 during the time set in this parameter initial cooling takes place according to the settings made in parameter t1 during the initial cooling the cooling signal diode blin...

Page 9: ...compressor safety functions such as CF minimum standstill time of the unit CA minimum operating time of the unit CC maximum working time of the unit Setting of these parameters can also affecton actua...

Page 10: ...alues are saved in the controller memory The programmable delay time of enabling this function allows the fresh milk to be pre cooled and thus does not take into account the maximum temperature when t...

Page 11: ...switch on the controller supply voltage again After performing the above described activities the controller will return to the factory settings therefore any changes made to the settings will be del...

Page 12: ...re t1 5 0 pre cooling temperature the function is active at the FC 0 setting see section 3 4 1 Table of settings for the cooling segment t2 5 0 recalling from the controller memory the maximum tempera...

Page 13: ...utton The unit then works in an automatic cycle according to the settings made The operation of the stirrer is indicated by the diode located above the button Pressing the button causes manual operati...

Page 14: ...CH 07 v 2 controller is activated only when cooling is switched off this activation is indicated by the appearance of the symbol on the display The washing segment may vary depending on the version of...

Page 15: ...imum number of steps in each program 50 minimum duration of one step 1 s maximum duration of one step 99 min range of the control temperature only MCH 07T v 2 version from 9 0 OC to 99 0 OC resolution...

Page 16: ...this function UAP parameter see section 4 3 1 Table of settings for the washing segment it is possible to temporarily limit the possibility of returning to the interrupted controller in range from 1...

Page 17: ...obtaining a signal from a hydrostatic This function is secured by setting the maximum time for pouring water in the event of mechanical suspension of the hydrostatic 4 2 12 Water heating control only...

Page 18: ...out active maximum time 2 setting the maximum loss of power time after which the controller will return to the interrupted operation UAP 0 off resuming operation is not time limited 1 the possibility...

Page 19: ...3 2 2 Selecting the function to be edited In section 4 3 1 Table of settings for the washing segment all available functions are given with their description and possible values to be set If you want...

Page 20: ...elay outputs hydrostatic input status duration of the step When programming or editing an existing program the following buttons perform the following functions changing the value of a setting upwards...

Page 21: ...it is recommended to create a table as shown in the description of the programs This will facilitate efficient programming 3 In the event of inactivity during programming the controller automatically...

Page 22: ...for the time programmed for a given step to elapse In order to set the test mode enter the settings and change the UEL parameter to 1 then confirm by pressing the S button The controller test operatio...

Page 23: ...p step duration CW ZW PP PML ZZ PMY 1 15 00 0 1 0 0 0 1 0 1 max time 2 03 00 0 0 1 0 0 1 0 0 3 00 30 0 0 1 1 0 1 0 0 4 15 00 1 0 0 0 1 1 0 1 max time 5 07 30 0 0 1 0 1 1 0 0 6 03 30 0 0 1 0 0 1 0 0 7...

Page 24: ...ZW PM PPR ZZ PMY 1 02 30 0 1 0 0 0 1 0 0 2 01 00 0 1 1 1 0 1 0 0 3 01 00 0 0 1 1 0 1 0 0 4 02 30 0 0 0 0 1 1 0 0 5 02 30 1 0 0 0 0 1 0 0 6 01 00 1 0 1 1 0 1 0 0 7 04 30 0 0 1 1 0 1 0 0 8 03 00 0 0 0 0...

Page 25: ...remains in a state of readiness for operation This is signaled by appearing symbol on the display The washing program is activated by pressing the start button and it is signaled by the symbol From th...

Page 26: ...d UPP parameter see section 4 3 1 Table of settings for the washing segment the user has the option of manually activating the vacuum pump or the stirrer operation relay no 4 Default settings or made...

Reviews: