Majestic  •  JADE32IN, JADE42IN, JADE42IL Installation Manual  •  2491-986 Rev. K

 

 •  10/18   

C.  Mantel and Wall Projections

WARNING! Risk of Fire! 

Comply with all minimum clear-

ances as specified. Framing closer than the minimums list

-

ed must be constructed entirely of non-combustible materi-

als (i.e., steel studs, concrete board, etc.).

Note:

 Measurement is taken from top of the 

opening, NOT the top of the fireplace.

Figure 10.3  Clearances To Combustibles Mantels Or Other 

Combustibles Above Appliance

Combustible Mantels

Non-combustible Mantels

Figure 10.4   Clearances To Non-Combustible Mantels Or Other 

Non-Combustibles Above Appliance

1/2 IN. 

THICK WALL 

SHEATHING

12 IN. MAX.

14 IN. MIN. BOTTOM OF MANTEL 

TO TOP OF APPLIANCE OPENING

COMBUSTIBLE MANTEL

APPLIANCE OPENING

12 IN.MAX.

1/2 IN. 

THICK WALL 

SHEATHING

14 IN. MIN. BOTTOM OF MANTEL 

TO TOP OF APPLIANCE OPENING

NON-COMBUSTIBLE 

MANTEL

6 IN. MAX.

NON-

COMBUSTIBLE 

MANTEL 

APPLIANCE OPENING

Summary of Contents for JADE32IN

Page 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could...

Page 2: ...lbows 19 E Measuring Standards 20 F Use of Flex Vent SLP FLEX Series 6 5 8 Inch 21 G Vent Diagrams 21 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 33 B Wall Penetration Framing Fire...

Page 3: ...ly installed ___________________________ Gas Section 9 Pg 49 51 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed a...

Page 4: ...on NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in resid...

Page 5: ...plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of...

Page 6: ...ted gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or lo...

Page 7: ...es Level Reciprocating saw Electric drill and bits 1 4 in Phillips 2 Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws Caulking material 300 F minimum continuous exposure...

Page 8: ...impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the f...

Page 9: ...nce Dimensions JADE32IN O Q P F G H T C X B A E S U V W TOP VIEW LEFT VIEW FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS D M R L N J K I HEAT MANAGEMENT SYSTEMS ACCESS BOTH SIDES Location In...

Page 10: ...25 7 8 657 T 50 1 2 1283 U 5 127 V 14 356 W 10 5 8 270 X 7 3 4 197 Location Inches Millimeters A 48 1219 B 43 1092 C 39 1 16 993 D 15 1 4 387 E 33 11 16 856 F 3 1 2 89 G 7 178 H 47 1 16 1195 I 9 13 16...

Page 11: ...32 in 28 3 16 14 1 8 33 1 8 6 7 8 9 13 16 19 7 8 26 7 8 mm 716 359 841 175 249 505 683 JADE42IN JADE42IL CFT 42 in 40 3 16 14 1 8 45 1 8 6 7 8 9 13 16 19 7 8 26 7 8 mm 1021 359 1146 175 249 505 683 D...

Page 12: ...VE FRONTS A B C D E F G JADE32IN PFF 32 in 26 3 16 14 1 8 37 1 2 4 5 8 9 7 8 24 7 16 29 1 8 mm 665 358 952 117 250 620 739 JADE42IN JADE42IL PFF 42 in 40 3 16 14 1 8 49 7 16 4 5 8 9 3 4 24 7 16 29 1 1...

Page 13: ...GN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 3 5 Appliance Locations 1 2 IN A E A C TOP VENT ONE 900 ELBOW ALC...

Page 14: ...ng with non combustible material pre installed on top and side Drywall or combustible materials mini mum 1 2 inch thick are designed to contact the non combustible material appliance as called out in...

Page 15: ...ith caulk with a minimum of 300 F continuous exposure rating to seal gaps Gas line holes and other openings should be caulked with caulk with a minimum of 300 F continu ous exposure rating or stuffed...

Page 16: ...DISCHARGE OPENING 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep in...

Page 17: ...ct vent termination i 3 ft U S A 6 ft Canada clearance to a mechanical powered air supply inlet All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below termina...

Page 18: ...5 8 inch and SLP FLEX7 7 inch venting systems DO NOT mix pipe fittings or joining methods from differ ent manufacturers SLP FLEX and SLP FLEX7 venting cannot be interchanged SLP FLEX 6 5 8 Inch Venti...

Page 19: ...e is allowed between two 45 elbows See Figure 4 4 Figure 4 5 shows the vertical and horizontal offsets for SLP elbows Figure 4 4 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G T H Y X X X Vent...

Page 20: ...See Section 12 A Figure 12 1 for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap See Figure 4 6 Verti...

Page 21: ...the necessary clearance to combustibles However the vent attachment point and the firestop loca tion are considered to be supports Figure 4 8 Flex Vent Pipe Generic Fireplace Shown 3 in CLEARANCE TERM...

Page 22: ...3 ft 914 mm 4 ft 1 2 m 3 ft 914 mm 5 ft 1 5 m 6 ft 1 8 m 4 ft 1 2 m 7 ft 2 1 m 15 ft 4 6 m 5 ft 1 5 14 ft 4 3 m H MAX 14 ft 4 3 m V H MAX 40 ft 12 2 m H MAX 15 ft 4 6 m V H MAX 40 ft 12 2 m CAUTION T...

Page 23: ...ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 4 ft 1 2 m 6 ft 1 8 m 4 ft 1 2 m 6 ft 1 8 m 15 ft 4 6 m 5 ft 1 5 15 ft 4 6 m H1 H2 MAX 15 ft 4 6 m V1 H1 H2 MAX 40 ft 12 2 m CAUTIO...

Page 24: ...ed 40 ft 12 2 m CAUTION The SLP HRC SS termination caps are not approved for use with these models May lead to elevated glass temperature that may cause tempered glass breakage JADE42IN JADE42IL V1 Mi...

Page 25: ...Top Vent Horizontal Termination continued Risk of Fire This vent configuration can ONLY be used for JADE42IN Natural Gas appliances WARNING CAUTION The SLP HRC SS termination caps are not approved fo...

Page 26: ...986 Rev K 10 18 26 Top Vent Vertical Termination No Elbow Figure 4 14 V1 60 ft Max 18 3 m Note Use SLP Series components only Note If installing a vertical vent termination off the top of the applian...

Page 27: ...anual bag Exhaust Restrictor Installation 1 JADE42IN JADE42IL Only Remove inner heat shield by removing two wing nuts from top front of heat shield and two screws that secure the heat shield to back w...

Page 28: ...4 6 m V1 V2 H MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H cannot exceed 40 ft 12 2 m JADE42IN JADE42IL V1 Minimum H Maximum V2 V1 V2 Minimum 1 ft 305 mm 2 ft 610 mm 2 ft 610...

Page 29: ...14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 cannot exceed 40 ft 12 2 m JADE42IN JADE42IL V1 Minimum H1 H2 Maximum V2 V1 V2 Minimum 1 ft 305 mm 1...

Page 30: ...2 MIN H2 MAX V3 MIN 2 1 2 ft 762 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m V1 H1 V2 V3 H2 Figure 4 18 Four 90 Elbows Top Vent Vertical Termination continue...

Page 31: ...qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the direction of certi fied professionals conduct a minimum of a NFPA 211 Lev...

Page 32: ...olid fuel or gas burning appliance May impair safe operation of this appliance or other appliances connected to the flue Vent this appliance directly outside Use separate vent system for this applianc...

Page 33: ...ust be field trimmed If wall thickness is greater than 7 5 8 in a DVP HSM B will be required SLP Pipe Shown 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides Heat Shield Wall Shield Firestop...

Page 34: ...the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRES...

Page 35: ...peratures may cause a fire JADE42IN JADE42IL 1 Remove two screws and discard See Figure 6 1 2 Fold up top heat shield to 90 degrees as shown in Figure 6 2 REMOVE SCREWS JADE32IN 1 Remove two screws an...

Page 36: ...the air register fan housing assembly Reference the Heat Zone Gas Kit Smart Wall TV Kit Heat Duct Kit or Heat Out Gas Kit instructions for the remaining installation steps Smart Wall TV Kit When a Sm...

Page 37: ...ve the lower cover panel by removing two screws located on the lower left and right sides of the appliance opening Retain screws Lift the lower cover panel up and out to remove 3 Locate the manual bag...

Page 38: ...f predrilling holes DO NOT penetrate inner pipe Required Commercial Multi family Multi level exceeding two stories or High Rise Applications All outer pipe joints must be sealed with high temperature...

Page 39: ...red length Figure 7 3 Slip Section Pilot Holes Figure 7 4 Screws into Slip Section Pilot hole Continue adding pipe as necessary following instructions in Assembling Pipe Sections NOTICE If slip sectio...

Page 40: ...rted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizon...

Page 41: ...12 LOWEST DISCHARGE OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Figure 7 11 Insert Bolt into Brackets NOTICE Failure to properly caulk the roof flashing...

Page 42: ...st overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 1...

Page 43: ...overlap could cause overheating and fire Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as appropriate for siding material at outsid...

Page 44: ...ate the interference 8 Electrical Information W H T W HT B L K BLK GRN wire inside box Copper ground attached to GRN screw with GRN wire 14 2WG Cover Plate outside firebox Romex Connector Figure 8 2 J...

Page 45: ...rcuit Incorrect wiring will override IPI safety lockout Refer to Figures 8 5 8 6 and 8 7 wiring diagrams This appliance is equipped with an IntelliFire Touch control valve which operates on a 6 volt 1...

Page 46: ...INTERMITTENT PILOT IGNITER NG 2106 169 HOT NEUTRAL JUNCTION BOX 110 120 VAC I S IFT CONTROL MODULE 2326 130 VALVE NG 2166 302 BLK BLACK RED GREEN ORANGE BRN RED RED WHITE WIRE ASSEMBLY 2118 170 WIRE...

Page 47: ...BRN BLK OPTIONS FAN GFK 160A IFT RC150 WIRELESS WALL SWITCH IFT RC400 REMOTE CONTROL IFT AUX AC MODULE CABLE 2326 152 RF MODULE 2326 120 RF MODULE 2326 120 2326 150 LED s GREEN MAIN WIRE HARNESS NOT...

Page 48: ...OT IGNITOR 2106 169 HOT NEUTRAL JUNCTION BOX 110 120 VAC I S IFT CONTROL MODULE 2326 130 VALVE NG 2166 302 BLK GREEN ORANGE BRN WIRE HARNESS 2326 132 AC MODULE CABLE 2326 152 RF MODULE 2326 120 IFT AU...

Page 49: ...th local codes if any If not follow ANSI Z223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installat...

Page 50: ...ompliance 2 Remove the two screws that secure the pilot shield to the burner bracket and remove the two screws that secure the pilot assembly to the burner bracket Remove the one screw that secures th...

Page 51: ...vertical runs See Figure 9 5 Loosen the 1 4 inch screw Twist the air shutter to adjust Air shutter may be opened for longer horizontal vent runs Tighten the 1 4 inch screw NOTICE If the flames appear...

Page 52: ...tions to ensure proper placement of fireplace into the sur rounding framing finishing materials Wall sheathing materials 1 2 in thick are specified in this installation manual to properly align with t...

Page 53: ...ning Ensure that the 1 8 inch gap is maintained between the factory installed non combustible board and the surrounding drywall See Figure 10 1 Se cure the drywall to the framing with screws a minimum...

Page 54: ...to Figure 10 2 for acceptable screw location and screw length requirements Self tapping screws up to one inch long can be installed through the nailing tab and outer 3 inch edges of the factory instal...

Page 55: ...e opening NOT the top of the fireplace Figure 10 3 Clearances To Combustibles Mantels Or Other Combustibles Above Appliance Combustible Mantels Non combustible Mantels Figure 10 4 Clearances To Non Co...

Page 56: ...6 Combustible or Non Combustible Mantel Leg or Wall Projections Unlimited Wall Length Acceptable on both sides of opening Note Clearance from opening to perpendicular wall MantelLegsOrWallProjectionsE...

Page 57: ...ck Stop finishing material flush with opening Overlap Fit CFT and PFF Decorative Fronts 0 Inches to 1 Inch Thick Finishing Material Figure 10 8 Overlap Fit Method CFT and PFF Decorative Fronts FACTORY...

Page 58: ...ront trim The auxiliary hanging brackets are not used and may be discarded See Figure 10 11 If the desired look is to exclude the outer decorative front trim finishing material can be installed up to...

Page 59: ...FT Front Without Outer Decorative Front Trim CFT Decorative Front Non Combustible Finish Material 1 6 Inches Thick 0 IN 0 IN CFT 0 IN Figure 10 12 Clearances to Appliance Opening Without Outer Decorat...

Page 60: ...d for positive placement when replacing the glass assembly See Section 11 I 11 Appliance Setup Figure 11 1 Fixed Glass Assembly D Install the Glass Refractory Optional An optional glass refractory kit...

Page 61: ...oken or scratched Replace as a complete assembly Replacing Fixed Glass Assembly The bottom glass latches have been designed to create a small gap between the glass clip and the face of the appliance S...

Page 62: ...rative fronts could cause fireplace to overheat IMPORTANT This fireplace requires an integral barrier to prevent direct contact with the hot viewing glass DO NOT operate the fireplace with the barrier...

Page 63: ...P45 45 Elbow SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16...

Page 64: ...m to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield...

Page 65: ...14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Term...

Page 66: ...DV 46DVA GCL Coaxial Colinear Appliance Connector 768 380A Stainless Steel Flex Pipe Required on JADE32IN COAXIAL to COLINEAR VENTING Figure 12 5 Coaxial to Colinear Vent Components SLP HHW2 Horizont...

Page 67: ...381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 mm MIN 35...

Page 68: ...mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit PVLP SLP Power Vent Low Profile Note Wire harnesses required to power...

Page 69: ...plied with the kit for installation Contact your dealer if you have questions Optional Log Kits Traditional or Driftwood Log kits are available for JADE32IN and JADE42IN JADE42IL Follow the instruc ti...

Reviews: