14
73D0129
DVKHL Series Gas Fireplace
VentInG InStaLLatIOn
terMInatIOn cLearanceS FOr BuILDInGS wItH cOMBuStIBLe
anD nOncOMBuStIBLe exterIOrS
Figure 9 -
Allowable Venting Chart
HOw tO uSe tHe Vent GrapH
The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimen-
sions of the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph below, locate
the point intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the fire-
place in accordance with same.
Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4 m) the horizontal run to the face of
the outer wall must not exceed 16' (4.9 m).
Sidewall Vent Graph showing the relationship between
vertical and horizontal dimensions for a Direct Vent flue
system.
Figure 10 -
Rear Wall Venting Graph
Horizontal dimension from the finished outside wall
to the center of the pipe on the fireplace
V
ertical Dimension From the Floor of Unit to the Center of the
Horizontal V
ent Pipe
Dimensions in
Feet
Combustible – 6" (152 mm)
Noncombustible – 2" (51mm)
V
G
G=6" (152mm)
F
F=6" (152mm)
V
V
G
G = Combustible 24"(610mm)
Noncombustible 18"(457mm)
Combustible &
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
V
H
J
C = Maximum depth of 48" (1219mm)
for alcove location
D = Minimum width for back wall of
alcove location
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)
E = Clearance from corner in alcove
location
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
E
V
D
C
C
Inside Corner
Alcove Location
Outside Corner
Balcony with No Side Wall
Balcony with Perpendicular
Side Wall
FP1951
termination clearances
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2 4 6 8 10 12 14 16 18 20
eg: A
FP2132
sidewall vent graph