DVB Series Direct Vent Gas Fireplace
54D0701
17
VeNt INstAllAtIoN
V
G
G=6" (152mm)
F
F=6" (152mm)
V
V
G
G = Combustible 24"(610mm)
Noncombustible 18"(457mm)
Combustible &
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
V
H
J
C = Maximum depth of 48" (1219mm)
for alcove location
D = Minimum width for back wall of
alcove location
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)
E = Clearance from corner in alcove
location
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
E
V
D
C
C
Inside Corner
Alcove Location
Outside Corner
Balcony with No Side Wall
Balcony with Perpendicular
Side Wall
FP1951
termination clearances
teRMINAtIoN cleARANces FoR BuIlDINGs WIth coMBustIBle
AND NoNcoMBustIBle exteRIoRs
Figure 12 -
Termination Clearances
hoW to use the VeNt GRAph
The Vent Graph should be read in conjunction with the following
vent installation instructions to determine the relationship between
the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exit-
ing through the outer wall. Using this dimension on the Sidewall
Vent Graph below, locate the point intersecting with the slanted
graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the fireplace in
accordance with same.
Example: If the vertical dimension from the floor of the fireplace
is 11' (3.4 m) the horizontal run to the face of the outer wall must
not exceed 14' (4.3 m).
Example: If the vertical dimension from the floor of the unit is
7’ (2.14 m), the horizontal run to the face of the outer wall must
not exceed 8
1
/
2
' (2.6 m).
Sidewall Vent Graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
2 4 6 8 10 12 14 16 18 20
eg: A
Dimensions in
Feet
20"
FP2248
sidewall vent graph
V
ertical Dimension from the floor of Unit to the Center of
the Horizontal V
ent Pipe
Horizontal Dimension from the Outside of
Termination to the Back of the Fireplace
Figure 13 -
Rear Wall Venting Graph