DVB Series Direct Vent Gas Fireplace
16
54D0701
VeNt INstAllAtIoN
V
V
V
V
V
V
V
V
D
L
E
B
C
F
B
B
B
B
B
M
I
A
A
J
H
G
A
Operable
Fixed
Closed
Fixed
Closed
Opera-
ble
K
A
A
A
G
FoR hoRIZoNtAl teRMINAtIoN
Inside corner
Detail
Vent Terminal
Air Supply Inlet
Area Where Terminals
are Not Permitted
Figure 11 - Horizontal Vent Termination Location
MINIMuM DIstANces
A = Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305 mm) minimum].
B = Clearance to window or door that may be opened [*12" (305 mm) minimum].
C = Clearance to permanently closed window [*minimum 12" (305 mm) recommended to prevent condensation
on window]
D
= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2)
feet (610 mm) from the centerline of the terminal [18" (457 mm) minimum].
E
= Clearance to unventilated soffits [12" (305 mm) minimum]. Clearance to vinyl soffit [30" (762 mm)].
F = Clearance to an outside corner.
Figure 12
G = Clearance to an inside corner.
Figure 12
H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally
from the centerline of the regulator.
I = Clearance to service regulator vent outlet [*3' (914 mm) minimum].
J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
[*12" (305 mm) minimum].
K = Clearance to a mechanical air supply inlet [*6' (1829 mm) minimum].
L
= Clearance above a paved sidewalk or paved driveway located on public property [
**
7' (2133 mm)
minimum].
M = Clearance under veranda, porch, deck or balcony, refer to
Figure 12.
*
As specified in CSA B149 Installation Codes. Note: Local codes or regulations may require different
clearances.
** A vent must not terminate directly above a sidewalk or paved driveway, which is located between two
single-family dwellings and serves both dwellings.
*** Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the
floor.
W
ARNING
Always maintain minimum clearances around vent systems. the minimum
clearance to combustibles for horizontal vent pipe are 3” at the top and 1” at
the sides and bottom of the vent system until the pipe penetrates the nearest
vertical wall (1” required). A 1” minimum clearance all around the pipe must be
maintained at outside wall and on vertical runs. Do not pack the open air spaces
with insulation or other materials. this could cause high temperatures and may
present a fire hazard.
*unless the vertical run is 7
Z\x
feet or higher (top vent units only), the clearances
for the horizontal run is 1” at the top.