background image

19

360DVS Series Direct Vent Fireplaces

10006326

2” (51mm). Secure termination to the wall with screws
provided, and caulk around the wall plate to weather-
proof.

One alternative to screwing the termination directly to
the wallis the use of expanding plugs or an approved
exterior construction adhesive.

Or, you may attach the termination with screws through
the inner body into the 4” (102mm) vent pipe; however,
for this method, you must extend the 4” (102mm) pipe
approximately 6” (153mm) beyond the outer face of the
wall.

Support the horizontal pipes with metal
pipe straps every 36” (914mm).

Below Grade Installation

When it is not possible to meet required vent terminal
clearances of 12” (305mm) above grade level, we
recommend using a starter kit. It allows installation
depth down to 7” (178mm) below grade level. Measure
7” (178mm) from the center of the horizontal vent pipe
as it penetrates through the wall.

NOTE:Ensure sidewall venting clearances are
observed. If venting system is installed below
ground, we recommend a window well with ad-
equate and proper drainage.

If installing a snorkel, a minimum 24” (610 mm)
vertical rise is necessary. The maximum horizontal
run with 24” (610mm) vertical pipe is 36” (914mm).
The measurement is taken from the collar of the
fireplace (or transition elbow) to the face of exterior
wall. See sidewall vent graph, Page 15, for extended
horizontal runs if the vertical exceeds 24” (610 mm).

1. Establish vent hole through the wall. (Fig. 24)

2. Remove soil to depth of about 16” (406mm) below

base of snorkel. Install window well (not supplied).
Refill hole with 12” (305mm) of coarse gravel,
leaving a clearance of about 4” (102mm) below
snorkel. (Fig. 28)

3. Install vent system.

4. Ensure a watertight seal is made around the vent

pipe coming through the wall.

5. Apply high-temperature sealant caulking (supplied)

around 4 in. and 7 in. snorkel collars.

6. Slide snorkel into vent pipes and secure to wall.

7. Level the soil so as to maintain a 4” (102mm)

clearance below snorkel. (Fig. 29)

Zero Clearance
Sleeve (if required)

Firestop

7” Pipe

24” (610mm)

Minimum

Screws

7TDVSNORK
(Snorkel)

Min. 4” (102mm)
Clearance

(Ground)

Window Well

Gravel

Foundation Wall

Drain

A minimum of 24” (610mm)
vertical pipe must be installed
when using the 7TDVSNORK
Kit.

The 22” (559mm) vertical rise
(center to center) of the snorkel
may be included for calculation
of maximum horizontal run.

FP1442

Fig. 28  Below grade installation.

Do not backfill around the snorkel.  A
clearance of at least 4” (102mm) must be
maintained between the snorkel and the
soil.

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel.
Fasten brackets to wall first, then secure to snorkel with
self drilling #8 x 1/2 sheetmetal screws. It will be
necessary to extend vent pipes out as far as protruding
wall face. (Fig. 29)

Snorkel

Foundation Wall

Watertight Seal
Around Pipe

Wall Screws

Sheet Metal Screws

CFM139

Fig. 29  Snorkel installation / recessed foundation.

Summary of Contents for 360DVS2

Page 1: ...ity of this or any other appliance If you smell gas 1 Open windows 2 Do not touch electrical switches 3 Do not try to light any appliance 4 Extinguish any open flame 5 Do not use any telephone in your...

Page 2: ...ion 16 Below Grade Installation 19 Vertical Through the Roof Application Installation 20 Twist Lock Venting Components 22 Operating Instructions Glass Information 23 Louvre Removal 23 Window Frame Ass...

Page 3: ...replace 10 The flow of combustion and ventilation air must not be obstructed in any way 11 When the fireplace is installed directly on carpeting vinyl tile or any combustible material other than wood...

Page 4: ...ical Access Gas Line Access J J K J J Fireplace Dimensions 360DVS2 Rear Vent Configuration Top Vent Configuration Ref Rear Vent Configuration Top Vent Configuration A 38 968mm 38 968mm B 43 1099mm 43...

Page 5: ...360DVS3 306DVSL 360DVSR Rear Vent Configuration Top Vent Configuration Ref Rear Vent Configuration Top Vent Configuration A 38 968mm 38 968mm B 40 1032mm 40 1032mm C 24 610mm 24 610mm D 24 610mm 24 6...

Page 6: ...s Ref Rear Vent Configuration Top Vent Configuration ROD 24 610mm minus two times finishing material thickness to be even with face of unit ROH 38 981mm Not to be framed until unit is set in place due...

Page 7: ...Configuration Model 360DVS3 360DVSL R 360DVS3 360DVSL R ROD See Note 1 See Note 2 See Note 1 See Note 2 ROH 38 981mm Not to be framed until unit is set in place due to 3 79mm allowance for flue collar...

Page 8: ...nt to prevent discoloration Clearance to Combustibles A B C D E V W X Y Z Louvre Assembly Top Fireplace Top of Combustion Chamber Bottom of Door Trim Mantel Shelf Mantel from Top Ref or Breast Plate R...

Page 9: ...h 360DVS2RN Nat Millivolt 38 000 26 600 360DVS2RP Prop Millivolt 38 000 28 500 360DVS2EN Nat 24V Hi Lo 38 000 26 600 360DVS2EP Prop 24V Hi Lo 38 000 28 500 360DVS3RN Nat Millivolt 38 000 26 600 360DV...

Page 10: ...x 2 Remove the plug socket assembly from the EB 1 box 3 Feed the supply line in from the out through the electrical knockout 4 Connect the ground wire of the supply line to the green screw of the sock...

Page 11: ...M Specialty Home Products must be used for this purpose NOTE When converting appliance to top vent ensure the insulation material referred to in step 3 is completely removed 4 Remove the 4 screws secu...

Page 12: ...0VA TRANSFORMER 24 VAC HOT BLACK WHITE WALL SWITCH WHITE OFF 1 2 3 5 6 8 9 MV MV VP PV GRD 24V SENSE SPARK 24V ORANGE RED GREEN BLACK FP1225 Fig 12 Honeywell ignition module Your fireplace is approved...

Page 13: ...regulator assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion...

Page 14: ...lation code USA Installations The venting system must conform with local codes and or current National Fuel Gas Code ANSI Z223 1 NFPA 54 Only venting components manufactured by CFM Corporation can be...

Page 15: ...nt graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system Fig 16 Sidewall vent graph Rear Wall Application When installed as a rear vent unit this appl...

Page 16: ...d realign the venting at the appliance flue collars Attach the termination to the wall as outlined in the instruction sheet supplied with the termination Vertical Sidewall Application It is very impor...

Page 17: ...elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizon...

Page 18: ...again secure joints as described in Connecting Vent Pipes section STEP 5 Measure the horizontal length requirement including a 2 51mm overlap i e from the elbow to the outside wall face plus 2 51mm o...

Page 19: ...runs if the vertical exceeds 24 610 mm 1 Establish vent hole through the wall Fig 24 2 Remove soil to depth of about 16 406mm below base of snorkel Install window well not supplied Refill hole with 12...

Page 20: ...ntal length must be reduced by 18 457mm Example Maximum horizontal length Zero elbows 10 3m 1 x 45 elbows 8 2 6m 2 x 45 elbows 7 2 1m A minimum of an 8 ft 2 43 m vertical rise Two 2 sets of 45 elbow o...

Page 21: ...til the venting is above the flashing Fig 34 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 32 11 Apply high temperature sealant to 4 and 7 collar...

Page 22: ...ion 45 Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90 Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic Ven...

Page 23: ...edge of frame out slightly and lift window frame assembly up and away from the fireplace 7 To reinstall the window frame assembly reverse this procedure Front Window Frame Assembly 1 Remove the top a...

Page 24: ...t into the underside For correct operation of the fireplace the logs must be correctly placed in the sequence described below 1 Unpack the logs from the shipping carton The logs are fragile handle the...

Page 25: ...near the center of the gas control valve Fig 42 and Fig 43 L O HI Turn counterclockwise to decrease flame height Turn clockwise to increase flame height Fig 42 Flame adjustment knob for Honeywell valv...

Page 26: ...ll around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do...

Page 27: ...d do not try to repair it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call...

Page 28: ...t supplied must be used to conduct this test 3 Pilot burning no gas to A Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wire across terminals at w...

Page 29: ...RES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY...

Page 30: ...ce Piezo Ignitor Supply Line Hooked Up Shutoff Valve Open PILOT STAYS LIT For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections Replace Thermopile Thermoco...

Page 31: ...ed in the conversion kit Air Shutter Retaining Screws Air Shutters FP1447 Fig 46 Air shutter adjustment 8 SIT Top Convertible Pilot Gently lift off pilot hood from the pilot NOTE Do not remove the spr...

Page 32: ...l gas used The only variations are in orifice sizes and component part numbers Your authorized service pro vider will ensure correct parts are used L O H I Regulator Cap Conversion Screw Pressure Regu...

Page 33: ...hould be per formed by a qualified technician 1 Turn off pilot light at gas valve side 2 Let fireplace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal...

Page 34: ...12 18 24 27 17 2 29 28 22 23 26 21 20 25 19 13 14 3a b 15a b 16a b 31a b 32 35 33 HI LO 34a b 25 36 37 30 1 1a 1b 1c 1d 1e 1f 1g CFM Specialty Home Products reserves the right to make changes in desi...

Page 35: ...E with cable electrode 10001824 10001824 10001824 10001824 7 Pilot SIT Top Convertible 10002266 10002266 10002266 10002266 8 Pilot Hood SIT Top Convertible 10002385 10002385 10002385 10002385 Orifice...

Page 36: ...ractory Lining vertical side wall N A N A 10006285 10006285 30 CR Bottom Kit w out Rear 10006257 10006257 10006257 10006257 Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174 Air Inlet...

Page 37: ...wiring 4 The power supply may be connected in two ways Method A Route the 6 lead fitted to the unit to a conveniently located wall socket Method B The EB I receptacle box Pt ZA1200 may be hard wired...

Page 38: ...mable 24 hour clock IMT Wall mounted thermostat control Decorative Trim Frame Kit The DV360TKMP Medium Trim Kit in polished brass is available for the 360DVS2 model only Each kit contains 4 polished b...

Page 39: ...upon inspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisi...

Page 40: ...83 84 65 360DVS3RP 62 4 83 84 65 360DVS3EN 62 4 83 84 65 360DVS3EP 62 4 83 84 65 360DVSLRN 62 4 83 84 65 306DVSLRP 62 4 83 84 65 360DVSLEN 62 4 83 84 65 360DVSLEP 62 4 83 84 65 360DVSRRN 62 4 83 84 65...

Reviews: