10
18NB/24NB Gas Log Set
81D0108
FLOOR CLEARANCE
The gas log heater must be installed at least 1
C\,
" above any combustible flooring material, such
as carpeting or tile, which is closer than 14" to the base of the fireplace. The minimum distance
must be maintained from the top surface of carpeting, tile, etc.
Figure 10
OR
The gas log heater may be installed nearer to the floor if a minimum of 14" of noncombustible
material such as slate or marble is installed between the base of the fireplace and the combus-
tible flooring.
Figure 11
Figure 10 -
Minimum Clearance above Combustible Flooring
FP2261
Min comb floor clear
Heater in Fireplace
or Firebox
Combustible
Material
1
C\,
” Minimum
FP2261
Figure 11 -
Minimum Clearance above Combustible Flooring with
Noncombustible Material Installed at Base of Fireplace
FP2262
Min noncomb floor clearance
14” Minimum
Heater in Fireplace
or Firebox
Combustible
Material
This Distance
May Now be
Less Than 1
C\,
”
FP2262