Majestic fireplaces Royal Collection WMC36 Homeowner'S Installation And Operating Manual Download Page 7

7

WMC Series Woodburning Fireplace

20000583

Chimney Supports

The chimney system is supported by the fireplace for 
vertical chimney heights less than 30' (9 m) above the 
hearth. Chimney supports are required if the vertical 
height exceeds 30' (9 m) with SK8 chimneys or 20' (6 
m) with 3-wall chimneys.  Locate chimney supports 
at ceiling holes or other structural framing at 30' (9 m) 
(SK8) or 20' (6 m) (3-wall) heights.  Spacing between 
chimney supports 

must not

 exceed 30' (9 m) (SK8) 

or 20' (6 m) (3-wall).  Use Chimney Support Model 
SKCS8 (SK8) and TCS8A (3-wall).  

(NOTE:  The 

chimney support cannot be mounted directly to 
the fireplace.) 

 Support provided by elbow straps ful-

fills the support requirement only if they are spaced as 
previously described. (A chimney support is 2

¹⁄₂

" long 

when installed.)
Angled chimney runs require a support every 6' (1.8m) 
in addition to the elbow straps. Chimney supports are 
used for this function. (Fig. 7) 

Chase Installation

A chase is a vertical boxlike structure which encloses 
the fireplace and/or chimney. Chases are typically built 
on the outside of the house with fireplace opening cut 
into the outer wall of a room. (Page 5, Fig. 3)
If you need help in determining fireplace location or 
how the chimney system should be run, contact your 
CFM Corporation dealer for assistance.

Insulating Fireplace Enclosure 

for Cold Climates

If you live in a cold climate, it is not required but 

highly recommended

 that you insulate fireplace 

enclosure to eliminate cold air penetration as much 
as possible.
Insulate base of fireplace with a noncombustible 
insulation rated for a minimum of 300°F.  Insulating 
is 

very important

 for outside wall installations over 

a concrete slab. If fireplace is installed on a platform, 
insulation should be placed on top of the platform 

before 

fireplace is set. (Fig. 8)

When a fireplace is installed in a chase or on a 
outside wall, enclosure should be treated like any 
outside wall in a home. Insulation should be installed 
on the inside wall as well as the outside wall(s). In a 
chase, it is also a good idea to install a firestop at the 
first ceiling level above the fireplace and enclose the 
chase with sheeting material. Insulation may then be 
installed above sheeting material to assure the space 
around the fireplace is totally protected. (Fig. 3)
When installing the chimney, 

DO NOT

 caulk between 

outer pipe and firestop. It is vital that some air be al-
lowed to flow through this very thin gap.

CAUTION: 

 WHEN INSTALLING A FIREPLACE IN 

AN INSULATED ENCLOSURE, BE SURE ALL RE-
QUIRED AIR SPACES ARE MAINTAINED. (Page 13, 
Fig. 18)

Installation

FP284

Fig. 7

  Chimney support installation.

FP284

MBUF CHIMNEY SUPPORT

1/28/99   djt

Chimney Sup-

port Strap

Chimney 

Support

FPC555

Platform insulation 

circulating model

1/28/99   djt

FPC555

Fig. 8 

  Insulating between platform and fireplace.

Cover Plate

Top Shield

Hard, Flat 

Surface

Insulation

Platform

Summary of Contents for Royal Collection WMC36

Page 1: ...e in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 4 07 Rev 21 FP583A WMC 12 18 98 WMC Series Woodburning Fireplace Homeowner s Insta...

Page 2: ...manufactured or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such c...

Page 3: ...Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series speci cations and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016m...

Page 4: ...Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak...

Page 7: ...imates If you live in a cold climate it is not required but highly recommended that you insulate replace enclosure to eliminate cold air penetration as much as possible Insulate base of replace with a...

Page 8: ...ns Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V swit...

Page 9: ...oration elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very impor...

Page 10: ...frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for install...

Page 11: ...e clearly snap together Once sections are snap locked in place it is extremely dif cult to get them apart Make sure the pipe is rmly snapped and locked together as each pipe section is mounted When in...

Page 12: ...raming hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Co...

Page 13: ...himney sec tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chas...

Page 14: ...oration Wall Shield Model SP40 or a speci cally built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and ca...

Page 15: ...rom manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R...

Page 16: ...of listed material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5...

Page 17: ...een the pipe and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from replace side NOTE When installing an ANSI Z21 11 2 ve...

Page 18: ...r replace 7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per replace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Si...

Page 19: ...n addition such action may void the coverage provided by the owner s insurance Accessories Contact your CFM Corporation distributor or dealer for nishing Mantels available in a wide selection of style...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Inc...

Page 21: ...the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclos...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: