Majestic fireplaces Royal Collection WMC36 Homeowner'S Installation And Operating Manual Download Page 6

6

WMC Series Woodburning Fireplace

20000583

Planning Information

Preplanning an installation is very important to ensure 
safety and to save time and money.  An installer must 
predetermine where a fireplace will be set and how the 
chimney system will be run.

Mounting the Fireplace

A fireplace may be mounted on the following surfaces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed be-

neath each of the four (4) corners of the fireplace.

The fireplace 

must

 be spaced 1/2" (13 mm) from a 

combustible back wall and 1/2" (13 mm) from a com-
bustible side wall or support. Refer to Page 14, Figure 
18.

Planning the Chimney Run

Determine how the chimney will be run, length of run 
and chimney components required to complete the 
job. (Fig. 4)  

Never

 install a chimney below minimum 

heights.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney 
height above the roof top. The “Ten Foot Rule” is a fire 
safety rule and not a draft rule.  It is recommended that 
you always meet or exceed the “Ten Foot Rule,” espe-
cially when installing a termination on a high pitch roof.  
(Fig. 6)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak 

of the roof is 10' (3 m) or less, the top of the chimney 
must be at least 2' (609 mm) above the peak of the 
roof, but never less than 3' (914 mm) in height above 
the highest point where it passes through the roof.

2. If a horizontal distance from the chimney to the peak 

of the roof is more than 10' (3 m), a chimney height 
reference point is established that is on the surface of 
the roof a distance of 10' (3 m) from the chimney in a 
horizontal plane. The top of the chimney must be at 
least 2' (609 mm) above the reference point, but never 
less than 3' (914 mm) in height above the highest 
point where it passes through the roof.

In planning a chimney system, it is important to know:
1.  The height of a chimney is measured from the 

hearth to the exit point on the termination.

2.  A chimney cannot be offset more than 30° from a 

vertical plane.

3.  A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4.  The maximum length of an angled run (total chim-

ney system) is 20' (6 m).  

5.  No more than 2 offsets (4 total 30˚ elbows in U.S./

or 2 total 45˚ elbows in Canada) per fireplace may 
be used.

6.  A guy wire stabilizer (not provided) is required for 

chimneys extending more than 6' (1.8 m) above a 
roof line.

L1

L1

LT

MODEL SK

2 WALL 

CHIMNEY

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

SK81

SK818

SK83

SK84

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

FP288A

MBUF-INSTALLED LENGTH

Triple wall

1/28/99   djt

TRIPLE

WALL

81

818

83

84

FP288A

Fig. 5 

 Installed lengths of chimney sections.

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC246

4/1/96

Reference

Point

AC246

Fig. 6 

  Ten Foot Rule illustration.

Summary of Contents for Royal Collection WMC36

Page 1: ...e in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 4 07 Rev 21 FP583A WMC 12 18 98 WMC Series Woodburning Fireplace Homeowner s Insta...

Page 2: ...manufactured or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such c...

Page 3: ...Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series speci cations and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016m...

Page 4: ...Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak...

Page 7: ...imates If you live in a cold climate it is not required but highly recommended that you insulate replace enclosure to eliminate cold air penetration as much as possible Insulate base of replace with a...

Page 8: ...ns Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V swit...

Page 9: ...oration elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very impor...

Page 10: ...frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for install...

Page 11: ...e clearly snap together Once sections are snap locked in place it is extremely dif cult to get them apart Make sure the pipe is rmly snapped and locked together as each pipe section is mounted When in...

Page 12: ...raming hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Co...

Page 13: ...himney sec tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chas...

Page 14: ...oration Wall Shield Model SP40 or a speci cally built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and ca...

Page 15: ...rom manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R...

Page 16: ...of listed material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5...

Page 17: ...een the pipe and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from replace side NOTE When installing an ANSI Z21 11 2 ve...

Page 18: ...r replace 7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per replace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Si...

Page 19: ...n addition such action may void the coverage provided by the owner s insurance Accessories Contact your CFM Corporation distributor or dealer for nishing Mantels available in a wide selection of style...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Inc...

Page 21: ...the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclos...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: