Majestic fireplaces Royal Collection WMC36 Homeowner'S Installation And Operating Manual Download Page 13

13

WMC Series Woodburning Fireplace

20000583

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney ter-
mination installed.  Refer to installation instructions 
provided with the chimney termination to find correct 
size of roof hole.
There must be an air space (1

¹⁄₂

" - SK8; 2" - 3-wall) 

between outermost portion of chimney sections and any 
adjacent combustible surfaces. (Combustible surfaces 
include burnable materials such as:  ceiling members, 
joists, flooring, combustible insulation and roof struc-
tures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the center of the 
point nail.  

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

Installing Top Housing

or Termination

Follow the installation instructions provided with the 
chimney termination you have selected.

Installing Chimney In a Chase

Refer to Page 4, Figure 3 for an illustration of a typical 
chase installation.

CAUTION:  Treatment of firestop spacers and con-
struction of chase may vary with type of building.  
These instructions are not a substitute for local 
building codes.  You must check your local building 
codes to determine specific requirements for your 
city or state. NOTE:  Other building materials may 
be required in addition to Firestop Spacers.

Finishing

CAUTION:  

All joints between the finished wall and 

the fireplace surround (top/sides) must be sealed with 
noncombustible material to prevent cold air leakage into 
the room. Only noncombustible material may be applied 
to the facing of the fireplace surround.  (Black painted 
area) (Fig. 21)

Finish Wall

Finish the wall with material of your choice.  

Do not 

install a combustible mantel shelf less than 12" 
(305 mm) from top of grille opening. Do not install 
a mantel face plate less than 6" (159 mm) from top 
of grille opening. 

(Fig. 23)

 

If a combustible material is 

Only noncombustible

material may be applied 

as facing to the black 

fireplace surround.

Wall 

Shield

Hearth 

Extension

0" Clearance

to Floor

Firestop

¹⁄₂

" Air 

Space

to Back

¹⁄₂

" Air 

Space

to Sides

FPC559

WMC

AIR SPACES

circulating models

1/29/99   djt

Front View

Side View

Standoff

Combustible framing material 

MUST NOT

 

penetrate AIR SPACE (shaded areas).

Air Space Clearances

¹⁄₂

" Air Space 

To Sides

1

¹⁄₂

" (SK8)

2" (3-wall)

Fig. 21

  Minimum clearances to combustibles.

FPC559

Summary of Contents for Royal Collection WMC36

Page 1: ...e in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 4 07 Rev 21 FP583A WMC 12 18 98 WMC Series Woodburning Fireplace Homeowner s Insta...

Page 2: ...manufactured or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such c...

Page 3: ...Dia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series speci cations and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt 1 6 m m 13mm 36 914mm 35 895mm 40 1016m...

Page 4: ...Surround Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...be at least 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak...

Page 7: ...imates If you live in a cold climate it is not required but highly recommended that you insulate replace enclosure to eliminate cold air penetration as much as possible Insulate base of replace with a...

Page 8: ...ns Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V swit...

Page 9: ...oration elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very impor...

Page 10: ...frame for ceiling chimney hole FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for install...

Page 11: ...e clearly snap together Once sections are snap locked in place it is extremely dif cult to get them apart Make sure the pipe is rmly snapped and locked together as each pipe section is mounted When in...

Page 12: ...raming hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Co...

Page 13: ...himney sec tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chas...

Page 14: ...oration Wall Shield Model SP40 or a speci cally built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and ca...

Page 15: ...rom manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R...

Page 16: ...of listed material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5...

Page 17: ...een the pipe and tube NOTE Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from replace side NOTE When installing an ANSI Z21 11 2 ve...

Page 18: ...r replace 7554338 7554338 6 Damper Knob Wood 7536177 7536177 7 Screen Pulls two per replace 5584139 5584139 8 Firebrick Left Side 3041104 3034102 9 Firebrick Back 3030102 3034104 10 Firebrick Right Si...

Page 19: ...n addition such action may void the coverage provided by the owner s insurance Accessories Contact your CFM Corporation distributor or dealer for nishing Mantels available in a wide selection of style...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Inc...

Page 21: ...the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclos...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: