Apart from dust, the router has strict requirements for SO2, H2S, NH3,
and Cl2 in the room, because these harmful gases speed up the eroding of
metals and the aging of some components.
The specific limitations are as follows:
Gas
Maximum value (mg/m
3
)
SO
2
0.2
H
2
S
0.006
NH
3
0.05
Cl
2
0.01
Anti-static
MP2800 router takes lots of measures in anti-static, but when the static
exceeds a certain volume, the circuits even the whole monitor are
damaged.
For router communication, static electricity originates from external
electric field of high-pressure like electricity cables and thunders, and
internal system such as floor material and chassis structure. To prevent
the damage caused by the static, do as follows:
§
Ensure proper equipment grounding
§
§
Maintain dustproof room
§
§
Keep suitable temperature & humidity
§
§
Wear anti-static equipment
§
§
Place the disassembled circuit board on the anti static workstation and
keep the face upturned or in the anti static bag
§
§
When viewing or removing the disassembled circuit board, touch the
edge of circuit board and avoid touching the components on the circuit
board.
Electromagnetic Environment
Requirements
The various interference sources, no matter from the exterior of devices or
application systems or from the interior, affect the devices through
capacitance coupling, inductance coupling, electromagnetic radiation,
public impedance (including grounding system) and lead (such as power
lines, signal lines and output lines).