Maico ER-AP Installation And Operating Instructions Manual Download Page 6

6 Safety instructions

6

 DANGER Danger if the relevant regula-

tions for electrical installations are not ob-
served.

Before removing the housing cover or removing
the fan insert and before installing the electrics,
switch off all supply circuits, switch of mains fuse
and secure it against being accidentally switched
back on again. Attach a warning sign in a clearly
visible place.
Be sure to observe the relevant regulations for
electrical installation; e.g. DIN EN 50110-1. In
Germany, particularly observe VDE 0100, with
the corresponding sections.
A mains isolation device with contact openings of
at least 3 mm at each pole is mandatory.
Only connect unit to permanently wired electrical
installation and with NYM-O or NYM-J cables,
depending on the unit variant, 3 x 1.5 mm² or 5 x
1.5 mm².
Units may only be operated using the voltage and
frequency shown on the rating plate.
Unit may be energized even when at a standstill
and may switch on automatically due to sensors
(time delay, humidity etc.). Maintenance and fault
finding only permissible when carried out by qual-
ified electricians.
The degree of protection stated on the rating
plate is only guaranteed if installation is under-
taken correctly and if the connecting cable is cor-
rectly guided through the stepped grommet (The
grommet must completely enclose the cable
sheathing). The fan insert must also be engaged
and the housing cover installed.

 DANGER Danger due to fire transmission

if an incorrect connection duct is connected to the
ER housing. Always use the correct duct material
for the respective ER housing.
if incorrect ceiling compound is used for exhaust
air systems with an intermediate ceiling (PAM-
GLOBAL RML or ceiling barrier system). Ensure
that the gap remaining between the main duct
and wall or ceiling is fully sealed with non-flam-
mable materials resistant to deformation, such as
concrete, cement mortar or plaster.
if the seal with the brickwork or wall boards is in-
correct. If used outside the shaft, ensure that the
gap remaining between the connection duct and
brickwork/wall boards is fully sealed with non-
flammable materials resistant to deformation,
such as concrete, cement mortar or plaster and
for the wall boards, special fire protection filler.
if the metal exhaust socket is incorrectly connec-
ted to the connection duct. 3 steel blind rivets are
prescribed for the connection with the exhaust
socket. These must not impair the shutter func-
tion. Before commissioning, ensure that the shut-
off shutter moves with ease.
if the metal shut-off shutter is not correctly inser-
ted and screwed down in the exhaust socket.
During installation, it is essential that the shut-off
shutter is correctly positioned and screwed down.
The soldered strut must be correctly inserted and
the shutter must move with ease.

 DANGER Risk of injury in case of dam-

aged unit.

Switch the unit off immediately if you discover
damage or faults that could endanger persons or
property.
Prevent from being switched back on until fully
repaired.

 WARNING Risk to health if filters are not

replaced or if there are no air filters.

Heavily soiled or moist air filters can accumulate
harmful substances (mould, germs, etc.). This
may also happen if the unit is shut down for an
extended period. If the air filter is missing, the
unit and air ducts become soiled.
Never operate the unit without air filters.
Only use original filters.
Regularly change air filter when a filter change is
indicated (LED or TimeStrip).
If the unit has not been used for a long time, al-
ways replace the air filters.

Summary of Contents for ER-AP

Page 1: ...Installation and operating instructions Surface mounted exhaust air system for single duct air ex traction according to DIN 18017 3 ER AP ER APB www maico ventilatoren com...

Page 2: ...ents in line with approval 11 9 1 1 Approval provisions 11 9 2 Permitted installation positions 11 9 3 ER APB Preparations for installa tion with fire protection require ments 12 9 3 1 Preparations fo...

Page 3: ...3 Preface Please read the instructions carefully before in stalling and using for the first time Follow the in structions Pass these instructions on to the owner for safekeeping Overview of ER AP APB...

Page 4: ...the necessary knowledge and experience in ventilation engineering The unit must be connected in accordance with the national technical approval Only a qualified electrician is permitted to work on the...

Page 5: ...may contaminate the unit and air ducts and reduce ef ficiency Never use unit to convey these substances NOTICE Damage to the unit when continu ously conveying steam saturated air Never use unit to con...

Page 6: ...M GLOBAL RML or ceiling barrier system Ensure that the gap remaining between the main duct and wall or ceiling is fully sealed with non flam mable materials resistant to deformation such as concrete c...

Page 7: ...at a point which is not permitted CAUTION Risk to health if unit is not cor rectly cleaned Clean the unit regularly at least every 2 years This is the only way of ensuring that the unit is running hyg...

Page 8: ...p ventilation ducts connected to the unit with a suitable adhesive tape to protect against corrosion inside the brickwork e g using cold shrink tape NOTICE Odours may escape from the ventila tion chan...

Page 9: ...l lable Mains cable mm ER AP 60 ER APB 60 Standard 9 1 no 3 x 1 5 ER AP 100 ER APB 10 Standard 9 1 yes 3 x 1 5 ER AP 60 VZ ER APB 60 VZ ER AP 100 VZ ER APB 100 VZ VZ circuit board 9 5 50 6 no 5 x 1 5...

Page 10: ...that virtually no air can flow into the living areas from the kitchen bathroom or WC A room from which the air is to be extracted must be fitted with a non closable free supply air cross section of a...

Page 11: ...ain duct in the shaft and the unit max 2 m long approval Steel folded spiral seams duct or flex ible alu minium duct between the main duct in the shaft and the unit max 2 m long approval Duct elbows i...

Page 12: ...ential that the remaining gap between the main duct and the wall or ceiling is completely sealed with non flammable materials that are res istant to deformation For example use concrete or cement mort...

Page 13: ...een the duct fastenings It is essential to observe the installation instructions Mounting prepara tions 10 Duct attachment with duct clamp alternatively duct attachment with clamping band Danger due t...

Page 14: ...in the wall or ceiling so that the lower part of the housing can be installed without warping Otherwise it may be that the fan insert can no longer be inserted into the lower part of the housing or t...

Page 15: ...r an air extraction system without fire protection 10 Housing installation 10 1 Wall installation lower part of housing 6 Lower part of housing 7 Cable grommet 10 Metal connection socket with ER APB s...

Page 16: ...d cable grommet 6 Pierce a round opening in the cable grommet with a grommet puncher 7 Guide the power cable into the terminal com partment such that the cable grommet fits around the cable sheathing...

Page 17: ...le 33 Fixing screw to be provided by the customer 34 Housing seal DANGER Risk of incorrect installation if non permitted mounting material is used Only secure connection duct to ceiling with per mitte...

Page 18: ...ning sign DANGER Danger from electric shock The unit will be damaged if installed incorrectly with too long a power cable If the cable feed is too long inside the housing the fan insert cannot be inst...

Page 19: ...alled the shut off shutter backflow preventer must close automatically For ER APB this must close automatically when the yoke spring used is pressed NOTICE Degree of protection not guaranteed if housi...

Page 20: ...e indicator value 6 11 Fit cover MAICO name on bottom right The cover must audibly click into place 13 Commissioning 1 Switch on mains fuse and remove warning sign 2 Run function test To do this switc...

Page 21: ...nents with dry cloth only 2 If the cover or upper part of the housing is very dirty clean with water Filter change Filter change interval every 3 to 6 months depending on the degree of soiling 1 Remov...

Page 22: ...se load to full load operation despite there being hu midity in the room No rapid increase in hu midity 7 in 2 minutes took place H model no longer switches back to base load operation or off even aft...

Page 23: ...ektroapparate Fabrik GmbH Steinbeisstra e 20 78056 Villingen Schwenningen Deutschland Tel 49 7720 694 445 Fax 49 7720 694 175 E mail ersatzteilservice maico de Spare parts can be ordered at www shop m...

Page 24: ...spose of the unit in an environmentally friendly way in compliance with the regulations valid in the country where you are 20 Wiring diagrams 20 1 Wiring diagrams ER AP APB ER AP 60 ER APB 60 ER AP 10...

Page 25: ...g The F fan is designed for installation in window less dark rooms The unit is switched on wire lessly through the brightness of the room lighting by a light control unit The unit starts up after ap p...

Page 26: ...ut again If the humidity falls below the saved reference value the overrun operation starts with an over run time of 15 minutes nominal load If the hu midity does not fall below the reference value wi...

Page 27: ...manually be switched to full load operation Switching off After switching full load operation off with S1 the unit continues in full load operation for an overrun time of 6 minutes If after this time...

Page 28: ...ues to run in full load operation until the humidity drops below the reference value After the 15 minutes of overrun time the fan switches back to base load operation is lower than the saved reference...

Page 29: ...29 If the room lighting is switched off with switch S2 the unit switches back into the base load level Switching off The unit can be switched off completely with switch S1 It doesn t matter what posit...

Page 30: ......

Page 31: ......

Page 32: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de D09 20_EN_DSW AS AV...

Reviews: