10 Housing installation
16
2. Mark fixing holes on wall: 3x fixing holes for
lower part of housing. For ER-APB, also 1x fix-
ing hole for tab (
ER-APB: Safety instructions for
installation of the fire protection shut-off
device [
) of metal exhaust socket. It is es-
sential that the permissible installation posi-
tions are observed.
3. Drill fixing holes and insert dowels. Suitable
mounting material is to be provided by the
customer.
4. Check ease of movement of shut-off shutter/
backflow preventer. When installed, the shut-
off shutter/backflow preventer must close
automatically.
5. When the power cable is surface installed at
position “S”, knock out the housing segment at
the nominal opening and cut small recesses
into the cross struts on the rear of the lower
part of the housing to route the ducts.
NOTICE Danger of short-circuits and damage
to the unit. If the power cable is incorrectly
fed or if the cable grommet is not fitted cor-
rectly, water may penetrate into the fan hous-
ing. The degree of protection cannot be guar-
anteed.
Pierce the cable grommet so that it tightly seals
the power cable. Guide the surface-mounted or
flush-mounted cables correctly into the intended
cable grommet.
6. Pierce a round opening in the cable grommet
with a grommet puncher.
7. Guide the power cable into the terminal com-
partment such that the cable grommet fits
around the cable sheathing completely.
DANGER Fire may spread if connection
duct is incorrectly installed.
Only use permitted duct material
Correctly attach connection duct to exhaust
socket.
8. Pull connection duct out of wall/shaft.
NOTICE The noise level will increase if the
housing seal is fitted incorrectly.
Ensure that the housing seal is correctly inserted
into the lower part of the housing all the way
round.
9. Check/ensure that housing seal is fitted cor-
rectly all the way round.
10.Slide connection duct up to stop above ex-
haust socket. Connection between connection
duct and exhaust socket must be leak-tight,
use cold-shrink tape for example.
Prescribed mounting material
Steel screw
Steel dowel
Masonry or
concrete
●
●
Panel building
materials
●
Keep gap remaining between the connec-
tion duct and wall board/brickwork/concrete
as small as possible.
11.Use 3 screws to secure the bottom part of
housing to the wall. For ER-APB, also screw
down tab of connection socket with fixing
screw. Suitable mounting material is to be
provided by the customer. Again check ease
of movement of shutter/backflow preventer.
When installed, the shut-off shutter/backflow
preventer must close automatically.