Maico AKE 100 Mounting And Operating Instructions Download Page 17

5. Product information │ UK 

 

17 

exchanged. This prevents moist air from 

flowing in. The fan is only switched on again 

once the climate conditions make 

dehumidification possible. 

 

 

Button 1 

(Taster 1) 

Reference value 

determination 

Button 2 

(Taster 2) 

Manual ventilation  

LED 1 

Operating mode 

LED 2 

Dehumidification status 

 

Display 

Function 

LED 1: On 

Automatic operating mode  

LED 1: Blinking*  Manual ventilation  
LED 1: Blinks 

twice with long 

pause 

Frost protection 

LED 1: Blinks 

three times with 

long pause 

Protection against 

insufficient humidity 

LED 2:  

On (in automatic 

mode) 

Active time during 

dehumidification 

(Fan on) 

LED 2: Off 

Passive time during 

dehumidification 

(Fan off) 

LED 2 
Blinking* 

Successful 

dehumidification achieved 

(resettable with button 1) 

 

* Simultaneous blinking: 

Simultaneous blinking of LED 1 or LED 2 

indicates an operating mode or function. If 

both LEDs blink simultaneously, there is a 

fault. See chapter Fault rectification. 

 

Successful dehumidification –  

Button 1 / Blinking LED 2: 

  

In the case that the room humidity is reduced 

by at least 0.2 g/m

3

, in comparison to the 

reference value, the AKE 100 signals 

successful dehumidification by LED 2 

blinking. A reference value of 9 g/m

3

 is set 

on-site. A new reference value can be set at 

any time by pushing button 1 during ongoing 

operation. Saving of the new reference value 

is confirmed by the LED 2 blinking briefly. 

 

Frost protection: 

To prevent the room from cooling down, 

the AKE 100 has a frost protection 

function. This means that the fan 

automatically switches off at inside room 

temperatures of less than 5 °C.

 

 

Protection against insufficient humidity: 

For reasons of health protection and energy 

efficiency, the AKE 100 offers a protection 

against insufficient humidity function. This 

protective function ensures the switching off 

of the fan if a relative humidity of less than 30 

% is reached. 

 

Manual ventilation – Button 2: 

The AKE 

100 switches the fan on and off automatically 

and in a manner optimised to demand. When 

off, the fan can be switched on manually with 

button 2 and manual ventilation therefore 

takes place. Manual operation is ended by 

again pressing button 2 or automatically after 

approximately 20 minutes. 
Optionally, manual operation can take place 

with an external button, see wiring diagram in 

Chapter 15. The fan cannot be switched off 

manually using the button when in the 

automatic operating mode. 

 

Summary of Contents for AKE 100

Page 1: ...ung Automatische Kellerentfeuchtung Mounting and operating instructions Automatic cellar dehumidification Notice de montage et mode d emploi D shumidification automatique des caves AKE 100 www maico v...

Page 2: ...Innengitter 9 Leitungst lle 10 Au enverschlussklappe Wandst ck 11 Au enverschlussklappe Au enst ck 12 Au en Klimasensor mit Sensorverbindungskabel Inhaltsverzeichnis 1 Lieferumfang 3 2 Qualifikation...

Page 3: ...ses Ger t ist ausschlie lich f r den h uslichen Gebrauch und hnliche Zwecke vorgesehen Das Ger t dient zur Entfeuchtung von Kellern Abstell und Vorratsr umen Austellungs r umen B ros Umkleidekabinen u...

Page 4: ...es Fl gelrad Haare Kleidung Schmuck etc k nnen in den Ventilator eingezogen werden wenn Sie sich zu nahe am Ventilator aufhalten Bei Betrieb unbedingt gen gend Abstand halten damit dies nicht passiere...

Page 5: ...mgang mit Ver packungsmaterialien Geltende Sicherheits und Unfallverh tungsvorschriften einhalten Verpackungsmaterial au er Reichweite von Kindern aufbewahren Zuluftnachstr mung innerhalb der Wohnung...

Page 6: ...gserfolg erreicht mit Taste 1 r cksetzbar Gleichzeitiges Blinken Ein gleichm iges Blinken von LED 1 oder LED 2 entspricht einer Betriebsart bzw Funktion Bei gleichzeitigem Blinken beider LEDs liegt ei...

Page 7: ...chaltkontakt mehr als 10 Sekunden geschlossen ist Das manuelle L ften mit einem externen Taster entspricht der Verwendung von Taster 2 Ist ein externer Schalter angeschlossen wird das manuelle L ften...

Page 8: ...in der Steigleitung einplanen Montagevorbereitungen wie in Kapitel 8 1 beschrieben vornehmen 8 3 Rohr 1 Kanten der Rohrinnenseite entgraten 2 Montagevorbereitungen wie in Kapitel 8 1 beschrieben vorne...

Page 9: ...bel mit Klebeband m glichst auf Unterseite in Wanddurchbruch Wandh lse befestigen F r die Verbindung mit der Steuerelektronik werden maximal 10 cm im Ventilatorgeh use ben tigt 9 3 Geh useeinbau Venti...

Page 10: ...rch Strom schlag Netzsicherung ausschalten ACHTUNG Ger tebesch digung bei Kurzschluss Schutzleiter und nicht ben tigte Adern isolieren 1 Im Ger t nur Einzeladern verlegen Dazu Mantel der Netzleitung a...

Page 11: ...ttel Abdeckung 4 und Design abdeckung 3 nur mit Wasser reinigen Keine aggressiven Reinigungsmittel verwenden 1 Innenteile des Ventilators nur mit einem trockenen Tuch reinigen 2 Bei stark verunreinigt...

Page 12: ...ng ausschalten 1 Abdeckungen entriegeln Pfeil und abnehmen 2 Elektronikabdeckung 6 entfernen 3 Rastnasen 3 Netzleitung entfernen 4 Ventilator ausbauen 14 Entsorgung Nicht in den Restm ll Das Ger t ent...

Page 13: ...rd 8 Internal grille 9 Cable grommet 10 External shutter wall piece 11 External shutter outer piece 12 External climate sensor with sensor connection cable Table of contents 1 Scope of delivery 14 2 S...

Page 14: ...intended for domestic use and similar purposes The unit serves to dehumidify cellars storage rooms showrooms offices changing rooms and similar rooms up to a floor area of approximately 25 m2 Operati...

Page 15: ...ermissible operation Operation is only permitted with a correct installation position see TOP on unit with mounted design cover and outer protective grille The fan may be operated only if the protec t...

Page 16: ...he AKE 100 is installed A room from which the air has to be extracted must be fitted with a non closable free supply air cross section of at least 150 cm e g with Maico door ventilation grille MLK 5 P...

Page 17: ...the AKE 100 signals successful dehumidification by LED 2 blinking A reference value of 9 g m3 is set on site A new reference value can be set at any time by pushing button 1 during ongoing operation...

Page 18: ...e manual ventilation when using an external switch 6 Environmental conditions and operating limits Permissible maximum temperature of air medium 40 C Sufficient supply air intake must be ensured durin...

Page 19: ...ver s locking hook unlock arrow using a screwdriver 2 Remove internal climate sensor 5 3 Remove the electronics cover 6 Unlock locking hook arrow with screwdriver 4 Fit supplied sealing strip centred...

Page 20: ...dowels 4 Push cable grommet 9 carefully out of housing and remove NOTICE Danger of short circuits and damage to the unit Water will penetrate if the power cable is incorrectly fed into the fan housin...

Page 21: ...le cores to 9 to 10 mm 2 Electrically connect power cable to spring clip 13 according to connection wiring diagram 14 also see wiring diagram in Chapter 15 3 Check position of cable grommet 9 It must...

Page 22: ...nd clean with water 3 Fit designer cover 3 12 Fault rectification Call on the services of a trained electrician any time there is a fault Repairs should only be carried out by a trained electrician DA...

Page 23: ...part materials that can be recycled and in part substances that should not end up in the domestic waste Dispose of the unit once it has reached the end of its service life according to the regulation...

Page 24: ...olet de fermeture ext rieur l ment ext rieur 12 D tecteur d atmosph re ext rieure avec c ble de raccordement du d tecteur Sommaire 1 Volume de fourniture 25 2 Qualification de l installateur sp cialis...

Page 25: ...c blage et en toute s curit conna t les dangers de l lectricit et peut les viter 3 Utilisation conforme Cet appareil est exclusivement r serv l usage domestique et similaires L appareil sert d shumidi...

Page 26: ...toutes les instructions de s curit Danger pour les enfants et les personnes ayant des capacit s physiques sensorielles ou psychiques r duites ou sans connaissances suffisantes L installation la mise...

Page 27: ...e bien visible La r glementation en vigueur pour l installation lectrique p ex EN 50110 1 et notamment pour l Allemagne la norme DIN VDE 0100 et les parties correspon dantes doivent tre respect es Pr...

Page 28: ...marre automa tiquement et un cycle de d shumidification commence p riode active L insufflation et l vacuation d air dure environ 10 minutes Le ventilateur est ensuite teint pendant 10 autres minutes...

Page 29: ...ode manuel s arr te par actionnement r p t du bouton 2 ou automatiquement au bout de 20 minutes Le mode manuel peut galement tre command par un bouton externe voir le sch ma de branchement au chapitre...

Page 30: ...ION Risque de court circuit et d endommagement de l appareil r sultant de la formation de condensat dans le bo tier de l a rateur Effectuer une isolation thermique des gaines d air dans les r gles de...

Page 31: ...ection externe 1 Introduire le bo tier de la protection externe 10 dans le per age de cloison la gaine murale 2 Aligner le bo tier horizontalement et marquer les orifices des chevilles 3 D poser le bo...

Page 32: ...r plus facilement le c ble secteur et de poser correctement le cache lectronique 6 Poser le manchon de c ble 9 dans les r gles de l art tanch ifier sur site si besoin est 5 Introduire le manchon de c...

Page 33: ...re ce qu elle ne bloque pas le montage du d tecteur d atmosph re int rieure ATTENTION Risque de court circuit et d en dommagement de l appareil P n tration d humidit en cas de mauvais positionnement d...

Page 34: ...s lectriciens qualifi s DANGER Danger de mort par lectrocution En cas d intervention sur le branchement lectrique d connecter le fusible secteur Les deux LED son teintes Pas de tension du secteur Cont...

Page 35: ...es substances recyclables ainsi que des substances qui ne doivent pas tre m l es aux ordures m nag res L appareil hors d usage doit tre limin conform ment aux prescriptions en vigueur dans votre pays...

Page 36: ...s L ften Optional button for manual ventilation Bouton en option pour la ventilation manuelle Z Anschluss f r optionales Zuluftelement z B ECA 11 E Connection for optional supply air element e g ECA 1...

Reviews: