Alarm messages are coded Axxx in the window title bar.

CODE 

MESSAGE 

When it occurs

A000 

EEPROM NOT WORKING 

In case of faults in the 
EEPROM memory

A001 

EEPROM DATA CORRUPT 

In case of faults in the 
EEPROM memory

A002 

PRESSURE SAFETY SWITCH 
ACTIVATED 

High pressure is over 18 
bar

A003 

ADC NOT WORKING 

After turning on the 
equipment

A004 

FAN NOT WORKING 

Only 
use

A006 

EAXXXX not working 

Electronic board 
problems

A009 

SENSORS ERROR: 

Sensors not connected 
or in short circuit

A032 

CIRCUIT STILL UNDER 
PRESSURE 

During vacuum, 
filling or leak test phase 
in vacuum

A033 

CIRCUIT LEAKAGE 

During vacuum, 
recharge or leak test 
phase

A034 

VACUUM LEVEL TOO LOW 

During 

A035 

BOTTLE EMPTY 

During the gas charging
and flushing phase

A036 

BOTTLE REFRIGERANT 
QUANTITY TOO LOW 

During the gas charging
and flushing phase

A037 

FURTHER REFRIGERANT 
CHARGE NOT POSSIBLE 

During gas 
phase

A038 

CIRCUIT LEAKAGE OR 
DISCONNECTED 

During flushing phase

Before approach the unit wear the personal protective systems 

The responsibility for the effects on people, animals or property resulting from inspection and repair work is entirely attributable to 

the technician who works on the equipment. The suggestions given on the following pages are only indicative and the 

manufacturer declines all responsibility for them. 

 

essages are coded Axxx in the window title bar. Alarms immediately terminate the procedure and prevent its resumption.

When it occurs 

Possible situations 

Possible solutions

In case of faults in the 
EEPROM memory 

EEPROM damaged 

Change the logic electronic 
board 

In case of faults in the 
EEPROM memory 

EEPROM damaged 

Change the logic electronic 
board 

High pressure is over 18 
bar 

High pressure (due to 
pressure on bottle or  
circuit to bottle closed) 
on refrigerant circuit 
between equipment’s 
compressor and internal 
bottle. 

Verify  
If internal 
is over 18 bar, wait for 
pressure reduction
disconnect equipment fro
mains, use safety protection, 
open equipment and make 
sure the valves between 
compressor and internal 
are open 

After turning on the 
equipment 

ADC fault 

Replacement of logic 
electronic board.

Only during R-1234yf 
use 

Fan not working properly 
(stopped or fan’s rpm 
not adequate) 

Stop use of the equipment 
check fan connections and 
if necessary, change fan and 
related cables with a new one 
change logic electronic board 
with new one.

Electronic board 
problems 

Faults on the electronics 
components or 
connections 

Updates the firmware

Sensors not connected 
or in short circuit 

Sensors disconnected or 
damaged. 

To check electrical 
connections or change with 
new spare part.

During vacuum, bottle 
filling or leak test phase 
in vacuum 

The vehicle A/C system 
is pressurized 

Recover the refrigerant gas 
from the vehicle before starting 
another vacuum phase.

During vacuum, bottle 
recharge or leak test 
phase 

Leakage in the circuit or 
in the vehicle fittings. 

Identify the leak position in the 
vehicle or connected system 
and have it repaired by trained 
and qualified staff according to 
local legislation. 

During charging phase 

Vehicle A/C system is 
pressurized 
notwithstanding the 
vacuum phase 

Identify the leak position in the 
vehicle or connected system 
and have it repaired by trained 
and qualified staff according to 
local legislation. 

During the gas charging 
and flushing phase 

Refrigerant gas is too 
low for the procedure to 
be completed 

Fill the internal tank

During the gas charging 
and flushing phase 

Gas amount in internal 
tank less than required 

Fill the internal tank

During gas charging 
phase 

Hoses not hooked up to 
A/C system; tap closed; 
vacuum not sufficient; 
presence of pressure in 
the circuit 

Caution: before proceeding, 
empty out the hoses.
Repeat the recovery procedure 
and increase the vacuum 
phase duration.

During flushing phase 

Leakages or 
obstructions in the 
circuit to be flushed 

Check the connection to the 
A/C system or identify 
in the circuit and have it 
repaired by trained and 
qualified staff according to 
local legislation.

property resulting from inspection and repair work is entirely attributable to 

the technician who works on the equipment. The suggestions given on the following pages are only indicative and the 

Alarms immediately terminate the procedure and prevent its resumption. 

Possible solutions 
Change the logic electronic 

Change the logic electronic 

If internal bottle pressure level 
is over 18 bar, wait for 
pressure reduction 
disconnect equipment from the 
mains, use safety protection, 
open equipment and make 
sure the valves between 
compressor and internal bottle 

 

Replacement of logic 
electronic board. 
Stop use of the equipment  
check fan connections and  
if necessary, change fan and 
related cables with a new one  
change logic electronic board 
with new one. 
Updates the firmware 

To check electrical 
connections or change with 

spare part. 

Recover the refrigerant gas 
from the vehicle before starting 
another vacuum phase. 
Identify the leak position in the 
vehicle or connected system 
and have it repaired by trained 
and qualified staff according to 
local legislation.  
Identify the leak position in the 
vehicle or connected system 
and have it repaired by trained 
and qualified staff according to 
local legislation.  
Fill the internal tank 

Fill the internal tank 

Caution: before proceeding, 
empty out the hoses. 
Repeat the recovery procedure 
and increase the vacuum 
phase duration. 
Check the connection to the 
A/C system or identify the leak 
in the circuit and have it 
repaired by trained and 
qualified staff according to 
local legislation. 

Summary of Contents for AIR-NEX 9380

Page 1: ...MAHLE AIR NEX 9380 9480 EN Service Manual A C Service Equipment...

Page 2: ...7 10 Equipment and simulator 17 11 Refrigerant fluid circuit 17 11 1 Refrigerant fluid circuit 17 11 2 Operational cycles 17 11 3 Receiving tank refrigerant cylinder 17 11 4 Manifold charts 18 11 5 Su...

Page 3: ...bal warming of the planet The release of refrigerant gas R134a into the atmosphere is forbidden by laws that were enacted within the framework of the Kyoto protocol For information only we will mentio...

Page 4: ...th an original spare part or equivalent by a MAHLE centre Before opening the service station extract completely the supply cable from the plug or you can get an electric shock Do not tamper with or by...

Page 5: ...g repairing it 2 3 Safety devices The A C service station is equipped with the following safety devices SAFETY PRESSURE SWITCH in case of excessive pressure SAFETY VALVE The safety valve opens when th...

Page 6: ...val of possible polluting substances from the A C system or parts of it Non condensable gas Refrigerant stored in gaseous phase including air and nitrogen 3 4 Guidelines for the handling of refrigeran...

Page 7: ...ed Refrigerant recovery and recharging Vacuum generation Flushing 4 2 Scope of delivery Description Service hose high pressure Service hose low pressure Quick release coupling high pressure Quick rele...

Page 8: ...ollowing icons are available on the display Icon Description Device connected via WiFi The residual refrigerant weight in kg and with visual bar to enable disable the bar by vertically swiping your fi...

Page 9: ...Vehicle selection OneClick Cycles Additional Functions Maintenance Setup Secured Service not available for user reserved only for customer service personnel Each function will be described in the nex...

Page 10: ...ype 13 18bar 1 4SAE Trip pressure 18 bar PED category Dir 2014 68 EU IV Pneumatic fittings Net length of external HP and LP hoses 4 5 m HP and LP pressure gauges Analog 80 mm pulse free 1 0 class Disp...

Page 11: ...imum devices required for correct handling shall be ensured as provided for by accident prevention provisions POSITIONING Place the unit in a stable place The location must be well ventilated with a g...

Page 12: ...plunger shall remain upright to be able to transfer liquid refrigerant for this type of tanks connect to the L liquid coupler Tanks without plunger have only one valve so they must be turned upside do...

Page 13: ...UV dye bottle Fig 1 Pos 9 it has to be extracted from its housing by means of the quick coupler on the top of the bottle slightly press downward the coupler ring nut to extract it standard UV Dye UV...

Page 14: ...in the garage data to be printed at the bottom of the cycle report LANGUAGE by selecting this entry any language present in the database may be set In case you choose a language with unintelligible c...

Page 15: ...apter alone not connected to the bottle station accessories kit when the next message is displayed Fig 16 LP quick coupler opening Turn the LP quick coupler clockwise to open it and press enter OK so...

Page 16: ...r opening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets into the LP hose Wait for the message to connect the reference gauge contained in the service kit and by ro...

Page 17: ...nt fluid circuit 11 1 Refrigerant fluid circuit For components and circuit layout ref APPENDIX 1 REFRIGERANT FLUID CIRCUIT 11 2 Operational cycles For components and circuit layout ref APPENDIX 2 OPER...

Page 18: ...system and closed that a pipe emptying operation has been made and the manifold has been completely emptied Fig 21 Manifold components NOTE on the manifold drawing above the position of the pressure s...

Page 19: ...product can get its maximum performance in terms of hold resistance For one s own and other people s safety the operator user of the Loctite 577 product must consider that it must be employed in well...

Page 20: ...AINTENANCEfromtheMAIN MENU press and scroll to MAINTENANCE and then select Fig 26 Maintenance screens Only for model AIR NEX 9380 REFRIGERANT TYPE CHANGE With this function allows the service assistan...

Page 21: ...to determine and store the at pressure value We recommend running this procedure every time the A C service station will be moved from a location to another with a different altitude 14 6 Self leak te...

Page 22: ...eplacement comply with the instructions outlined below 1 disconnect the HP and LP hoses from other systems circuits or vehicles and close the quick couplers 2 wait the ends the hoses emptying 3 confir...

Page 23: ...the lid of the printer as shown note press the green led as in picture and only after that open the lid 2 Position the roll of paper inside the housing in the rotation direction indicated in the pictu...

Page 24: ...dies in charge after the results of the previous checks performed of commissioning or not establish different The checks must be performed by the bodies in charge in the country where the station is c...

Page 25: ...c components for use of R1234yf He will also carry nfigurations and verifications required by the the MAINTENANCE 14 16 Replacing white sample filter Refrigerant identification unit The need to replac...

Page 26: ...electronic power board Replacement of power supply board 15 2 Extraordinary maintenance 15 2 1 Replacement of component connected to refrigerant circuit The components pressurised equipment constituti...

Page 27: ...Evident damage to board components and circuits For the replacement of the board it is recommended to position the new board alongside the one to be replaced Disconnect and reconnect the cables in se...

Page 28: ...OF A C SERVICE STATION AIR NEX 9380 9480 ECO LOCK optional LP quick coupler and red Active Oil Protection kit 2 pcs New Oil 1 UV dye rts are available through the Service Centers USING NON ORIGINAL UN...

Page 29: ...en 29 AIR NEX 9380 9480 APPENDIX 1 REFRIGERANT FLUID CIRCUIT AIR NEX 9380 9480 H...

Page 30: ...AIR NEX 9380 9480 30 en APPENDIX 2 REFRIGERANT FLUID CIRCUIT AIR NEX 9380 9480 OPERATIONAL CYCLES Uncondensable gases H...

Page 31: ...en 31 AIR NEX 9380 9480 Recovery cycle H...

Page 32: ...AIR NEX 9380 9480 32 en Vacuum H...

Page 33: ...en 33 AIR NEX 9380 9480 Recharge H...

Page 34: ...Dye1 input load cell dye 1 10 LC New Oil1 input load cell new oil 1 11 PS Tank input pressure sensor tank 12 LC Ex Oil input load cell 13 PS LP input pressure sensor LP 14 PS HP input pressure sensor...

Page 35: ...EX 9380 9480 APPENDIX 4 AIR NEX 9380 9480 ELECTRICAL CONNECTION POWER ELECTRONIC BOARD AND POWER SUPPLY POWER ELECTRONIC BOARD POWER SUPPLY BOARD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21...

Page 36: ...ed oil draining 9 OUT H Heat exchanger fan 10 OUT I HP LP solenoid interconnection valve 11 OUT N Solenoid valve for draining of tank s uncondensable gases 12 OUT V Vacuum pump 13 OUT V Vacuum solenoi...

Page 37: ...ing to the 20 minutes vacuum time Gas leakage from internal or compressor check for leaks from valves R or check compressor functioning Pressure sensor not Altitude compensation and or full pressure c...

Page 38: ...Change vacuum pump oil When the filter capacity is the filter capacity is finished Change filter with new one During the setting of the inner tank charge amount Amount required greater than that avai...

Page 39: ...disconnected or damaged To check electrical connections or change with new spare part During vacuum bottle filling or leak test phase in vacuum The vehicle A C system is pressurized Recover the refrig...

Page 40: ...le fittings leak test Empty the vehicle follow the procedure guided by the displayed messages A048 HP LEAKAGE During the gas recovery and hoses emptying phase At the end of the gas charging in the E3...

Page 41: ...is phase Analisys not possible Check with virgin refrigerant bottle if the refrigerant gas identifier is working properly If yes and the refrigerant of the car is not R1234yf empty in a safety way and...

Page 42: ...MAHLE Aftermarket Italy S p A Via Quasimodo 4 a 43126 Par ma ITALY 2019 11 07...

Reviews: