Periodic checks 

A/C  service  stations  (pressure  equipment  set)  must  be 
checked over regularly as provided by local legislation. 
The frequency for the periodic requalification check of:

 

functioning  of  the  container  and  of  the  pressure 
equipment set and of the related protection/safety 
devices/accessories  is  established  by  local 
legislation and related technical standards; 

 

integrity  of  the  container  and  of  the  pressure 
equipment  set  is  established  by  local  legislation
and related technical standards;   

withstanding that: 

 

the national laws in force of the country where the 
station  is  commissioned  do  not  provide  for  a 
higher frequency (lower period of time); 

 

the  bodies  in  charge,  after  the  results  of  the 
previous  checks  performed  (of  commissioning  or 
period  requalification)  do  not  establish  different 
frequencies. 

The  checks  must  be  performed  by  the  bodies  in  charge  in 
the  country  where  the  station  is  commissioned,  in 
compliance  with  the  national  laws/rules  and  the  related 
procedures.  Please  identify  and  contact  these  bodies  in 
order  to  establish  performance  times  and  modes  of 
commissioning 

and 

periodic 

requalification 

checks 

(integrity, functioning, or any other scheduled checks).
Depending on local legislation, the checks may be extended 
to 

other 

components 

to 

verify 

the 

metrolo

characteristics  of  the  integrated  instrumentation  and  the 
presence of essential equipment and accessories.  
Here below, some possible checks on components subject 
to the PED directive are outlined. 

 

VESSEL 20l - Category III (Dir. 2014/68/EU) 

    

 

Make  sure  no  corrosion  or  leakage  is  present; 
under normal conditions of use, the vessel life is at 
least  20  years  (in  the  absence  of  wear  and  other 
types of damages).  

 
SAFETY VALVE 20bar R 1/4 NPT - Category IV (
2014/68/EU) 

 

 

If  the  automatic  safety  valve  trips,  contact 
technical  service  to  have  the  unit  checked  over, 
resolve  any  problems  and  replace  the  valve  if 
necessary. 

 

| AIR-NEX 9380/9480 

A/C  service  stations  (pressure  equipment  set)  must  be 
checked over regularly as provided by local legislation.  
The frequency for the periodic requalification check of: 

functioning  of  the  container  and  of  the  pressure 

ction/safety 

devices/accessories  is  established  by  local 

 

integrity  of  the  container  and  of  the  pressure 
equipment  set  is  established  by  local  legislation 

national laws in force of the country where the 

station  is  commissioned  do  not  provide  for  a 

the  bodies  in  charge,  after  the  results  of  the 
previous  checks  performed  (of  commissioning  or 

not  establish  different 

The  checks  must  be  performed  by  the  bodies  in  charge  in 
the  country  where  the  station  is  commissioned,  in 
compliance  with  the  national  laws/rules  and  the  related 
procedures.  Please  identify  and  contact  these  bodies  in 

rder  to  establish  performance  times  and  modes  of 

commissioning 

and 

periodic 

requalification 

checks 

(integrity, functioning, or any other scheduled checks). 
Depending on local legislation, the checks may be extended 
to 

other 

components 

to 

verify 

the 

metrological 

characteristics  of  the  integrated  instrumentation  and  the 

 

Here below, some possible checks on components subject 

Make  sure  no  corrosion  or  leakage  is  present; 
under normal conditions of use, the vessel life is at 
least  20  years  (in  the  absence  of  wear  and  other 

Category IV (Dir. 

valve  trips,  contact 

technical  service  to  have  the  unit  checked  over, 
resolve  any  problems  and  replace  the  valve  if 

 

SUCTION UNIT - Art. 4.3  (Dir. 2014/68/EU

 

Make sure no corrosion and leakages are present.

 
PRESSURE SWITCH 13/18bar 1/4SAE 
2014/68/EU) 

 

 

Check  presence  of  the  device  with  references  indicated 
above, wholeness of connection cables and connector, and 
the  correct  connection  to  the  equipment  printed  circuit 
board.  In  case  the  pressure  switch  must 
contact  the  technical  customer  service  that  will  check  the 
equipment and remove any defect.

 

HOSES 

 

Periodically  check  that  the  external  charging  hoses,  red 
(HP)  and  blue  (LP),  are  in  good  order  and  undamaged.  In 
case  damages  to  the  hoses  are  detected,  stop  using  the 
station  and  contact  the  technical  customer  service  for  the 
related replacement. 

OTHER CHECKS 

 

Verify  that  the  lubricants  (pump  oil)  and  filters  (dryer)  have 
been  replaced  according  to  the  scheduled  periodicities  for 
a proper functioning of the equipment.

 
 

 

NEX 9380/9480 | 24   en

 

Dir. 2014/68/EU) 

 

Make sure no corrosion and leakages are present. 

 - Category IV (Dir. 

 

Check  presence  of  the  device  with  references  indicated 
above, wholeness of connection cables and connector, and 
the  correct  connection  to  the  equipment  printed  circuit 
board.  In  case  the  pressure  switch  must  intervene,  please 
contact  the  technical  customer  service  that  will  check  the 
equipment and remove any defect. 

Periodically  check  that  the  external  charging  hoses,  red 
(HP)  and  blue  (LP),  are  in  good  order  and  undamaged.  In 

are  detected,  stop  using  the 

station  and  contact  the  technical  customer  service  for  the 

 

Verify  that  the  lubricants  (pump  oil)  and  filters  (dryer)  have 
been  replaced  according  to  the  scheduled  periodicities  for 

unctioning of the equipment. 

Summary of Contents for AIR-NEX 9380

Page 1: ...MAHLE AIR NEX 9380 9480 EN Service Manual A C Service Equipment...

Page 2: ...7 10 Equipment and simulator 17 11 Refrigerant fluid circuit 17 11 1 Refrigerant fluid circuit 17 11 2 Operational cycles 17 11 3 Receiving tank refrigerant cylinder 17 11 4 Manifold charts 18 11 5 Su...

Page 3: ...bal warming of the planet The release of refrigerant gas R134a into the atmosphere is forbidden by laws that were enacted within the framework of the Kyoto protocol For information only we will mentio...

Page 4: ...th an original spare part or equivalent by a MAHLE centre Before opening the service station extract completely the supply cable from the plug or you can get an electric shock Do not tamper with or by...

Page 5: ...g repairing it 2 3 Safety devices The A C service station is equipped with the following safety devices SAFETY PRESSURE SWITCH in case of excessive pressure SAFETY VALVE The safety valve opens when th...

Page 6: ...val of possible polluting substances from the A C system or parts of it Non condensable gas Refrigerant stored in gaseous phase including air and nitrogen 3 4 Guidelines for the handling of refrigeran...

Page 7: ...ed Refrigerant recovery and recharging Vacuum generation Flushing 4 2 Scope of delivery Description Service hose high pressure Service hose low pressure Quick release coupling high pressure Quick rele...

Page 8: ...ollowing icons are available on the display Icon Description Device connected via WiFi The residual refrigerant weight in kg and with visual bar to enable disable the bar by vertically swiping your fi...

Page 9: ...Vehicle selection OneClick Cycles Additional Functions Maintenance Setup Secured Service not available for user reserved only for customer service personnel Each function will be described in the nex...

Page 10: ...ype 13 18bar 1 4SAE Trip pressure 18 bar PED category Dir 2014 68 EU IV Pneumatic fittings Net length of external HP and LP hoses 4 5 m HP and LP pressure gauges Analog 80 mm pulse free 1 0 class Disp...

Page 11: ...imum devices required for correct handling shall be ensured as provided for by accident prevention provisions POSITIONING Place the unit in a stable place The location must be well ventilated with a g...

Page 12: ...plunger shall remain upright to be able to transfer liquid refrigerant for this type of tanks connect to the L liquid coupler Tanks without plunger have only one valve so they must be turned upside do...

Page 13: ...UV dye bottle Fig 1 Pos 9 it has to be extracted from its housing by means of the quick coupler on the top of the bottle slightly press downward the coupler ring nut to extract it standard UV Dye UV...

Page 14: ...in the garage data to be printed at the bottom of the cycle report LANGUAGE by selecting this entry any language present in the database may be set In case you choose a language with unintelligible c...

Page 15: ...apter alone not connected to the bottle station accessories kit when the next message is displayed Fig 16 LP quick coupler opening Turn the LP quick coupler clockwise to open it and press enter OK so...

Page 16: ...r opening Turn the LP quick coupler clockwise to open it and press enter OK so that air gets into the LP hose Wait for the message to connect the reference gauge contained in the service kit and by ro...

Page 17: ...nt fluid circuit 11 1 Refrigerant fluid circuit For components and circuit layout ref APPENDIX 1 REFRIGERANT FLUID CIRCUIT 11 2 Operational cycles For components and circuit layout ref APPENDIX 2 OPER...

Page 18: ...system and closed that a pipe emptying operation has been made and the manifold has been completely emptied Fig 21 Manifold components NOTE on the manifold drawing above the position of the pressure s...

Page 19: ...product can get its maximum performance in terms of hold resistance For one s own and other people s safety the operator user of the Loctite 577 product must consider that it must be employed in well...

Page 20: ...AINTENANCEfromtheMAIN MENU press and scroll to MAINTENANCE and then select Fig 26 Maintenance screens Only for model AIR NEX 9380 REFRIGERANT TYPE CHANGE With this function allows the service assistan...

Page 21: ...to determine and store the at pressure value We recommend running this procedure every time the A C service station will be moved from a location to another with a different altitude 14 6 Self leak te...

Page 22: ...eplacement comply with the instructions outlined below 1 disconnect the HP and LP hoses from other systems circuits or vehicles and close the quick couplers 2 wait the ends the hoses emptying 3 confir...

Page 23: ...the lid of the printer as shown note press the green led as in picture and only after that open the lid 2 Position the roll of paper inside the housing in the rotation direction indicated in the pictu...

Page 24: ...dies in charge after the results of the previous checks performed of commissioning or not establish different The checks must be performed by the bodies in charge in the country where the station is c...

Page 25: ...c components for use of R1234yf He will also carry nfigurations and verifications required by the the MAINTENANCE 14 16 Replacing white sample filter Refrigerant identification unit The need to replac...

Page 26: ...electronic power board Replacement of power supply board 15 2 Extraordinary maintenance 15 2 1 Replacement of component connected to refrigerant circuit The components pressurised equipment constituti...

Page 27: ...Evident damage to board components and circuits For the replacement of the board it is recommended to position the new board alongside the one to be replaced Disconnect and reconnect the cables in se...

Page 28: ...OF A C SERVICE STATION AIR NEX 9380 9480 ECO LOCK optional LP quick coupler and red Active Oil Protection kit 2 pcs New Oil 1 UV dye rts are available through the Service Centers USING NON ORIGINAL UN...

Page 29: ...en 29 AIR NEX 9380 9480 APPENDIX 1 REFRIGERANT FLUID CIRCUIT AIR NEX 9380 9480 H...

Page 30: ...AIR NEX 9380 9480 30 en APPENDIX 2 REFRIGERANT FLUID CIRCUIT AIR NEX 9380 9480 OPERATIONAL CYCLES Uncondensable gases H...

Page 31: ...en 31 AIR NEX 9380 9480 Recovery cycle H...

Page 32: ...AIR NEX 9380 9480 32 en Vacuum H...

Page 33: ...en 33 AIR NEX 9380 9480 Recharge H...

Page 34: ...Dye1 input load cell dye 1 10 LC New Oil1 input load cell new oil 1 11 PS Tank input pressure sensor tank 12 LC Ex Oil input load cell 13 PS LP input pressure sensor LP 14 PS HP input pressure sensor...

Page 35: ...EX 9380 9480 APPENDIX 4 AIR NEX 9380 9480 ELECTRICAL CONNECTION POWER ELECTRONIC BOARD AND POWER SUPPLY POWER ELECTRONIC BOARD POWER SUPPLY BOARD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21...

Page 36: ...ed oil draining 9 OUT H Heat exchanger fan 10 OUT I HP LP solenoid interconnection valve 11 OUT N Solenoid valve for draining of tank s uncondensable gases 12 OUT V Vacuum pump 13 OUT V Vacuum solenoi...

Page 37: ...ing to the 20 minutes vacuum time Gas leakage from internal or compressor check for leaks from valves R or check compressor functioning Pressure sensor not Altitude compensation and or full pressure c...

Page 38: ...Change vacuum pump oil When the filter capacity is the filter capacity is finished Change filter with new one During the setting of the inner tank charge amount Amount required greater than that avai...

Page 39: ...disconnected or damaged To check electrical connections or change with new spare part During vacuum bottle filling or leak test phase in vacuum The vehicle A C system is pressurized Recover the refrig...

Page 40: ...le fittings leak test Empty the vehicle follow the procedure guided by the displayed messages A048 HP LEAKAGE During the gas recovery and hoses emptying phase At the end of the gas charging in the E3...

Page 41: ...is phase Analisys not possible Check with virgin refrigerant bottle if the refrigerant gas identifier is working properly If yes and the refrigerant of the car is not R1234yf empty in a safety way and...

Page 42: ...MAHLE Aftermarket Italy S p A Via Quasimodo 4 a 43126 Par ma ITALY 2019 11 07...