To find the electrical center point of pot rotation, use a digital multimeter type ohm meter to measure from
the white wire (wiper), to the red or black wire.  Turn the potentiometer shaft until the meter reads 500
ohm.  Install the DFP-2 sensor so the meter reading is 500 ohms when the follower arm is halfway
through its travel.

5.3   Dancer Control Setup and Tuning

The control adjustments marked on the label without an underline or box are the only ones needed for
dancer adjustment.  Stop Time and Stop Multiplier apply to all operating modes and are not distinctively
marked.

1)  Set the following switch and 22-turn potentiometers to the settings given below:

F

switch

PD

P

      

full 

Clockwise

D

      

mid 

rotation 

(approximately 

11 

turns)

CORE

     

full 

Counter 

Clockwise

STOP TIME

   

full 

Counter 

Clockwise

STOP MULT

   

full 

Counter 

Clockwise

2)  With the machine running with web, adjust the

POS1

 pot to center the dancer arm.

3)  Adjust the

 D

 pot to minimize dancer arm oscillations.   The direction to adjust

D

 to minimize

oscillations is system dependent.

4)  If dancer arm oscillations cannot be eliminated, turn the

 P

 pot Counter Clockwise and repeat step 3.

Calibration is complete, and the DFC-A is ready for operation.

Optional Adjustments:

Integrator.  Many machines run quite successfully after the above adjustments have been made.  If the
dancer arm moves too much while the roll changes size, the integrator can be turned on to keep the
dancer centered.

The control adjustments marked with a box apply to a dancer with integrator.

5)  Set the

 I

 pot full Clockwise.

6)  With the machine stopped, set the

F

switch to         .  This turns the integrator on.

7)  Run the machine near full roll and at a slow speed and use the

 pot to center the dancer.

Clockwise rotation of            moves the dancer up, towards an empty dancer condition.

8)  Turn the    pot Counter Clockwise until the dancer begins to oscillate around  the setpoint position.

Then, turn the    pot Clockwise until the oscillation stops.

The RUN/STOP input must be used if the integrator is on (

F

switch in          position).  The RUN/STOP

input should be closed (terminals 9 and 10) when the machine starts its deceleration.  The DFC-A keeps
the integrator on until Stop Time expires.   Stop Time may be increased by Clockwise rotation of the

STOP TIME

 pot.  The STOPPED indicator illuminates when the Stop Time has expired.  While the

STOPPED indicator is illuminated the DFC-A provides a hold level output that may be adjusted by
turning the             pot.

POS2

POS2

I

I

PID

HOLD

Summary of Contents for DFC-A

Page 1: ...m or Dancer control applications The DFC A provides a 0 to 10 vdc or 4 to 20 ma output to control a current to pressure transducer or a motor drive in torque mode Terminals are provided for the connec...

Page 2: ...r DFP 2 roll diameter sensor 10 kohm tension potentiometer All inputs and outputs have the negative lead referenced to ground 4 2 Sensor Setup See Figure 3 The DFP or DFP 2 position sensor should be a...

Page 3: ...ME full Counter Clockwise STOP MULT full Counter Clockwise 2 Set the external TENSION pot full Clockwise 3 Position the follower arm on an empty core 4 Adjust the CORE pot to obtain zero on the remote...

Page 4: ...E may be adjusted from 0 2 to 60 seconds 5 0 Dancer Applications 5 1 Electrical Connections Figure 5 shows the connections that are required for the basic dancer system They are 24 vdc power Current T...

Page 5: ...peat step 3 Calibration is complete and the DFC A is ready for operation Optional Adjustments Integrator Many machines run quite successfully after the above adjustments have been made If the dancer a...

Page 6: ...ating Counter Clockwise until the dancer stabilizes The POS1 pot may require readjustment several times in order to keep the dancer roll centered DEFINITION In the following steps the user will have t...

Page 7: ...for the Remote tension control DFP DFP 2 position sensor not wired properly or wires shorted Verify position sensor is wired properly and follow the calibration procedure in section 4 3 Voltage betwe...

Page 8: ...alibrated Follow the calibration procedure in section 5 3 Output full on or full off DFC A in PID mode and RUN STOP switch is not wired properly Verify RUN STOP switch wiring PID mode needs a RUN STOP...

Page 9: ...tude 0 to 2000 m Compatible Residual Current Device Types A or B IEC755 Worst Case Fault Current 2 0 amp dc Inputs Signal DFP or DFP 2 Potentiometer 1 to 10 kohm watt minimum Tension Potentiometer 10...

Reviews: