SHUTTING DOWN THE GENERATOR
Check with personnel using power supplied by the generator and let them know the power is going to be turned off.
Make sure the power shutdown will not create any hazards by accidentally turning off equipment that needs to be
kept on (pumps, compressors, lights, etc.).
1. Remove all loads from the generator by opening all circuit breakers (turn to “OFF/O”).
2. Let the engine run for approximately five minutes to allow it to cool down.
3. Push the red “ENGINE STOP” button. Pressing “ENGINE STOP” will result in the generator going into
the shutdown cycle and starting a 15 second shutdown timer called “Stop Value.” If the unit does not
shut down within 15 seconds, a “Stop Fail” alarm will be displayed on the Liquid Crystal Display (LCD)
window.
4. Move the “CONTROL ON/OFF” toggle switch to the “CONTROL OFF/O” position.
Note:
For extended storage time, disconnect the battery. Refer to the engine operator’s manual for extended storage
requirements.
MDC CONTROLLER INFORMATION DISPLAYS, FUNCTIONS AND RESET
The Magnum Digital Controller (MDC) constantly monitors vital generator and engine functions for a number of
operation, alarm and fault conditions. When a fault condition occurs, the engine will shut down automatically and the
Liquid Crystal Display (LCD) window will show the fault that has caused the shutdown. To resume operation, the
fault condition must be resolved. To reset the controller and resume operation, press the “FAULT RESET” button.
The operation of the Magnum Digital Controller (MDC) is divided into the following sections:
MAGNUM DIGITAL CONTROLLER (MDC) – GENERATOR OPERATIONAL STATUS
The Magnum Digital Controller (MDC) displays the operational status of the generator using the following codes:
No.
Engine State
Description
1
AfterCool
Engine aftercooling, cooling pump output is closed.
2
Cooling
The unit is cooling before stop.
3
Cranking
Engine is cranking.
4
EmergMan
Emergency Manual gen-set operation.
5
Init
Autotest during controller power on.
6
Loaded
The unit is running at nominal speed and GCB OPEN/
CLOSE is closed.
7
Not Ready
The unit is not ready to start.
8
Pause
Pause between start attempts.
9
Prestart
Prestart sequence in process, prestart output is closed.
10
Ready
The unit is ready to run.
11
Running
The unit is running at nominal speed.
12
Shutdown
Shutdown alarm is activated.
13
Starting
Starting speed is reached and the
idle timer
is running.
14
Stop
Stop.
No.
Electrical State
Description
1
StabilTO
Stabilization Timeout