MAGNUM DIGITAL CONTROLLER (MDC)
The Magnum Digital Controller (MDC) is an enhanced digital generator controller used to start, stop and monitor the
operation of the generator and the engine. The controller constantly monitors vital generator and engine functions
for a number of pre-programmed alarm and fault conditions. When a fault condition occurs, the engine will shutdown
automatically and the Liquid Crystal Display (LCD) window will display the fault that caused the shutdown; to resume
operation the fault condition must be resolved. The controller has the ability to provide the display readout in English
and Spanish; other languages are available. A screen print out of the display screen is also available. This controller
also records a history of the units performance which may be viewed at any time and will not be lost when the
controller is powered down.
The MDC panel consists of five sections, including: the “CONTROL ON/OFF” toggle switch and fine voltage adjustment
screw; the “OPERATION” keypad; the LCD window; the “DIAGNOSTICS” keypad; and the “STATUS” Light Emitting
Diodes (LED’s).
DIGITAL CONTROLLER FEATURES AND FUNCTIONS
1.
The “CONTROL ON/OFF” Toggle Switch and Fine Voltage Adjustment Screw
•
“CONTROL ON/OFF” Toggle Switch:
This toggle switch powers-up the control panel and the controller.
•
Fine Voltage Adjustment Screw:
This screw may be adjusted to set the generator output voltage after the
voltage selector switch has been changed from one phase to another. This adjustment
MUST
be accom-
plished within 45 seconds of startup, during the “V Detect,” so that the unit does not experience a shutdown
alarm for “over and under voltage.” Refer to
“Fine Voltage Adjustment ” on page 21
.
2.
The “OPERATION” Keypad
•
“ENGINE START” Button:
The unit must be in the “MAN” mode in the upper left corner of the LCD window
display and the “READY/MANUAL” LED lit in the “STATUS” portion of the controller. Press the green “ENGINE
START” button to start the unit.
•
“ENGINE STOP” Button:
Press the red “ENGINE STOP” button to shut down the unit and start the “Stop
Value” timer.