background image

 

45

PROBLEM 

CAUSES 

SOLUTIONS 

 

?  

Room blower will not operate. 

 

 

 

 

 

 

 

 

 

 

No power to stove. 

 

 

No power to control board. 

 

 

Blower has overheated due to dirt 
on blades or in motor. 

 

 

Blower is defective. 

 

 

9

 

Check to see that the unit is 
plugged into the wall outlet. 

 

9

 

Check to see if your circuit breaker 
has “tripped”. 

 

 

9

 

Clean blades and motor, have a 
MagnuM tech replace blower if 
needed.

 

 

?  

Soot or fly ash in the house. 

 

 

Cleaning the glass, particularly 
when the unit is operating. 

 

Leakage on the joints between the 
combustion fan, exhaust pipe and 
“PL” vent.  This will be evident by 
dust on the heat exchanger tubes 
and the impeller of the room fan. 

 

Using a conventional vacuum for 
cleaning. Ash will bypass the filter 
and enter the room. 

 

Negative pressure in home sucking 
ash/soot out of venting and unit. 

 

 

Fireplace insert installation:

 If the 

existing fireplace opening was not 
thoroughly cleaned and painted 
before the insert was installed, then 
the room fan may be picking up the 
fireplace dust, soot or ash and 
blowing it into the home. 

 

9

 

Clean the glass when the unit is not 
running. 

 

9

 

Seal any leaks in the exhaust 
system with RTV high temperature 
silicone sealer. 

 

9

 

Use approved ash vacuum. 

 

9

 

Correct negative pressure situation. 

 

 

9

 

Pull the insert away from the 
fireplace opening. Thoroughly 
clean the opening and paint the 
inside of the opening with latex or 
an inexpensive spray paint to hold 
the finer particles of dust. 

 
?  

Buildup of soot on glass, venting and 

heat exchangers. 

 

 

Dirty fuel. 

 

Inadequate air supply. 

 

Negative pressure in home. 

 

Air wash plugged or out of 
adjustment. 

 

9

 

Make sure you use clean fuel. 

9

 

Pull manual draft control out 
slightly to insure there is app. ½” of 
fuel in firepot. 

9

 

Install outside air to unit. Verify 
home has adequate make-up air. 
(Suggested 6” make-up air into 
home.) 

9

 

Clean air-wash located on bottom 
of glass door. 

CAUTION:  

When performing any internal electrical maintenance  

 

Moving parts inside of the cabinet may cause injury. 

 

HOT parts.  Do not operate the unit with panel open. 

 

Risk of electrical shock.  Disconnect power before servicing unit. 

 

In the event of component failure, replace with original factory equipment. 

IMPORTANT: Electrical work must be performed by a Factory authorized technician.  

 

Summary of Contents for Elite WIN-ACI

Page 1: ...ressure All chimney connections elbows and fittings must be airtight Proper venting practices must be followed Consult with a venting professional 9 Ashes must be disposed of in a metal container with...

Page 2: ...es 36 Glass Maintenance Adjustment Removal and Replacement 37 Circuit Board Functions 38 39 Setting the Draft 40 Wiring Diagram AC 41 42 Draft Slide Gate Adjustment 43 Solar Panel Connections 43 Ignit...

Page 3: ...American Energy Systems Inc manufacturer of the MagnuM Winchester Appliances reserves the right to alter its products their specifications and or price without notice Safety tested and EPA exemption...

Page 4: ...tove or it could be that there is a serious lacking of good quality air in the home caused by negative pressure If you have done any remodeling or if this is a newer home it is a very real possibility...

Page 5: ...enance cleaning 9 A working smoke detector must be installed in the same room as this product 9 It is recommended that a fire extinguisher class a b c be installed close to the appliance 9 Flammable o...

Page 6: ...proper dryness 9 Check your corn for foreign objects Your stove warranty will not cover damage done to your stove due to foreign objects in the fuel supply 9 Do not carry your corn supply over into t...

Page 7: ...e to foreign objects in the fuel supply 9 Store your wood pellets in a dry place to prevent them from absorbing excess moisture 9 Vacuum the hopper out after every 6 7 bags to eliminate buildup of saw...

Page 8: ...hown later in the installation manual Make sure that the shroud is with the unit when you get it The following diagram will show how to install the legs on the Leg Unit The legs are wrapped up and pac...

Page 9: ...otection must be 3 8 minimum thickness non combustible material or equivalent extending beneath heater and to the front side rear as indicated CHIMNEY AND CONNECTOR 3 LISTED PELLET VENT ONLY NOTE REGA...

Page 10: ...nough to ignite grass plants or shrubs located in the vicinity of the termination The grade surface must not be a lawn Distance from bottom of termination and public walkway is 7ft 2 1m minimum 9 Dist...

Page 11: ...gth should not exceed 30 feet Diagram 11 1 Component Equivalent Length Equivalent Pipe Length Horizontal Straight Pipe Actual Length in ft x 1 0 Horizontal Pipe 1 x 2 1 3 ft Vertical Straight Pipe Act...

Page 12: ...epending on length of run elbows and configuration you will have to increase the size of the fresh air intake Typically you would increase from 3 to 4 over 10 of run or more than 2 elbows 4 Only non c...

Page 13: ...er local building codes fire codes and the safety listing tag on the inside hopper lid An outside air source must be connected to the stove and can be brought in through the sidewall or vented crawl s...

Page 14: ...E FOLLOWING REQUIREMENTS ARE MANDATORY FOR INSTALLATION IN A MOBILE HOME 1 Stove must be permanently bolted to the floor 2 Stove must have permanent outside air source 3 Stove must be permanently elec...

Page 15: ...s per the pellet vent manufacturer s instructions Connect the pipe and lock the joints as directed by the pellet vent manufacturer and secure the vent pipe to the flue collar on the back of the stove...

Page 16: ...te The pipe lengths shown are for reference only Your actual pipe length requirements may differ SINGLE WALL PIPE SHALL NOT BE USED FOR ANY INSTALLATION HORIZONTAL INSTALLATION SHALL BE A MAXIMUM OF 5...

Page 17: ...s and presence of all necessary parts including a chimney cap prior to making the connection 3 This stove may be connected to an existing ceiling mounted factory built chimney with a diameter of 4 6 o...

Page 18: ...s ash buildup premature failure of exhaust system staining of the house siding and serious creosote buildup This installation should not be used in a cold climate area Storm Collar Note This type of i...

Page 19: ...er from the upper position to the lower position see details below 7 Connect the thermostat wires to the two terminals on the back of the control panel When the room temperature drops below the thermo...

Page 20: ...20 MAGNUM WIN INSERT INSTALLATION...

Page 21: ...21 WIN INSERT INSTALLATION cont Siding Use only rigid Pellet Vent pipe Framing Chimney cap Storm Collar Seal Plate 3 75mm Minimum Clearance Around vent 6 150mm min 16 375mm minimum 6 150mm minimum...

Page 22: ...st use some type of support bolt to hold and level the unit not provided For a raised Hearth you can have a decorative skirting made by your installer to finish off the front of the unit The skirting...

Page 23: ...resh air intake either out the back of the fireplace cavity or down and out to an outside air source Running the fresh air up and out the top of the chimney can cause excessive draft issues Your insta...

Page 24: ...24...

Page 25: ...25 Fireplace Insert Shroud Installation Diagram...

Page 26: ...26 Thermostat wire connection Low voltage thermostat Molex Plug 24 volt thermostat hookup...

Page 27: ...he control center Please NOTE Power on light glows amber when on Heat level indictor LED red per heat level setting Heat level up adj button Exhaust Draft Blower trim adjustment button ON OFF control...

Page 28: ...pot When fuel begins to drop regularly release auger button the auger is primed NOTE The viewing door ash pan door and hopper door must be closed and or latched during operation or vacuum will not be...

Page 29: ...l Unplugging the unit will prevent this from happening OPERATING INSTRUCTIONS Without using system igniter NOTE Each time the stove is started the firepot should be checked for debris and clear air ho...

Page 30: ...tage or interruption lasting longer than 5 seconds the On Off button must be pushed to re engage the auger If needed re light the unit NOTE If the fire is burning too fast and the fuel is being burned...

Page 31: ...ired burn rate by moving the control center to the desired operating position B Select the most efficient burn by adjusting the air damper control rod An air damper closed too much will produce a lazy...

Page 32: ...ASH TO ESCAPE INTO THE ROOM AIR HOWEVER VACUUMING Use an approved Ash vacuum system IS RECOMMENDED OCCASIONALLY TO AID IN SEASONAL CLEANING AND KEEP THE UNIT FREE OF EXCESS ASH DISCARD THE VACUUM BAG...

Page 33: ...ason dust and ash may collect on the blades of the combustion blower Periodically they should be inspected vacuumed and clean The combustion blower is accessed by opening the stove s right side panel...

Page 34: ...they should be inspected and vacuumed clean The combustion blower is accessed by removing the inspection caps or the exhaust manifold cover See figure below Never operate the stove without the inspec...

Page 35: ...they will be ignited in the chimney and produce damage to the chimney or even possibly destroy the home Clean the chimney as often as needed and never go more than one 1 year without a flue cleaning...

Page 36: ...nit overheats it will shut itself down safely The unit may not be restarted until it has cooled and the reset button is depressed See Thermodisk location section If the auger does not turn after clean...

Page 37: ...glass is not sitting on top of any obstructions The glass will break when tightening the screws if the glass is on the gasket Hold the glass toward the top of the door glass channel when tightening C...

Page 38: ...tton allows for a low high fuel setting fine tune adjustment on the all 5 settings When pushing the auger trim button select either the heat level up button or heat level down button depending on the...

Page 39: ...the damper is on the back of the unit you trying it up will increase draft and turning to a 90 deg position will decrease A little movement of the knob goes a long way to changing the flame It may tak...

Page 40: ...40 AC MODEL WIRING DIAGRAM WARNING DISCONNECT POWER BEFORE SERVICING THIS UNIT...

Page 41: ...w degrees at a time until the proper operation of the unit is achieved NOTE This adjustment must be made by a qualified MagnuM Service Technician When rotating the slide gate be careful not to damage...

Page 42: ...installing the new igniter hand tighten the igniter and then apply slight pressure to secure the threads Do not over tighten the igniter assembly If you over tighten the igniter assembly it may ruin...

Page 43: ...ates 9 Change to a better grade of fuel if necessary 9 Check that damper control knob is adjusted properly Pull out to increase fire burn 9 Push ash cleanout slides in 9 Check gasket seal around the d...

Page 44: ...witch or relay 9 Check contents of the hopper Add fuel if necessary 9 Check all operations fuses re set manual high limit thermodisk 9 Clean out auger system 9 Have your MagnuM reseller diagnose the p...

Page 45: ...the home 9 Clean the glass when the unit is not running 9 Seal any leaks in the exhaust system with RTV high temperature silicone sealer 9 Use approved ash vacuum 9 Correct negative pressure situation...

Page 46: ...fuel Lack of clean combustion air Dirty or plugged stove or venting Poor exhaust vent configuration Negative pressure present in the home Exhaust fan motor going out Use combustion enhancement system...

Page 47: ...RP2098 MagnuM Baby Countryside WIN Arched Glass w gasket R 131 Glass Gasket 5 16 separate per foot R 133 Door Gasket 3 8 separate per foot MF3626 Door Handle Assembly RP2070 WIN Gold Door complete doo...

Page 48: ...aims submitted verbally or without the required information and documentation Before exercising this warranty an AES representative the place where the product was purchased or AES approved person mus...

Page 49: ...49 SERVICE RECORD DATE SERVICE OR CLEANING PERFORMED This record must be sent in when any warranty claims are made...

Reviews: