©
2010 Magnum Energy, Inc
.
Table 6, Inverter Default Settings
03 Battery AmpHrs:
This setting allows you to input the battery bank
size in amp hours. This provides information to the charger on how
long to charge the batteries in the Absorb Charging stage.
04 Battery Type:
This setting identi
fi
es the type of batteries being
used in the system. This provides information to the charger to
determine what voltage level to use to charge the batteries.
05 Charge Rate:
T
his setting can be used to turn off the charger, limit
the amount of current that the charger can use (leaving more current
available to power loads); or, to ensure small battery banks are not
overheated because of a charge rate that is too high.
06 VAC Dropout:
Sets the minimum AC voltage that must be pres-
ent on the AC input before the unit transfers from Standby Mode to
Inverter Mode. This protects the AC loads from utility outages and
brown-outs.
The ME-RC50 remote also provides the following features:
allows you to enable an equalize charge for certain battery
types
displays the inverter/charger’s operating status
provides fault information for troubleshooting
•
•
•
3.0 Operation
31
Function
Default Settings
Search Watts
5W
LowBatCutOut
10.0 VDC (
MM1524AE
-
20.0 VDC)
Battery AmpHrs
400 AmpHrs
(Absorb Time = 120 minutes)
Battery Type
Flooded - Liquid Lead Acid
(Bulk = 14.6 VDC, Float = 13.4 VDC)
(MM1524AE - Bulk = 29.2 VDC, Float = 26.8 VDC)
Charge Rate
100%
VAC dropout
80VAC