2010 Magnum Energy, Inc
.
20
2.0 Installation
AC Output Wiring
CAUTION:
The inverter’s AC output must never be con-
nected to an AC power source. This will cause severe
damage to the inverter and is not covered under war-
ranty.
When hardwiring the output of the inverter, a cable must be routed
from the inverter’s output to an AC distribution panel (sub-panel)
that provides overcurrent protection to the loads powered by the in-
verter. Connect the AC output to this distribution panel as described
below:
1. Remove the 1/2” knockout on the AC Output Connection
(see Figure 4, Item 15) – use a utility knife to cut thru the round
slot.
2. Discard this knockout and install a 1/2” strain relief in the AC OUT
opening. You may need to
fi
le the opening edge for proper
fi
t.
3. Run a 2-conductor plus ground cable through the strain relief in
the AC OUT opening. Refer to Table 4 for the minimum wire size and
the overcurrent protection required for the AC output wiring.
AC IN
AC O UT
Strain
reliefs
A C
Ground
In/Out
(g re e n)
N eutral
In
(w h ite)
H ot
Out
(re d)
N eutral Out
(w h ite w/b la ck
strip e )
H ot
In
(b la ck)
Figure 11, AC Wiring Connections