Operation
3.0 Operation
The MSH-RE Series inverter has two normal operating routines: Inverter mode, which powers
your loads using the batteries, and Standby mode, which transfers the incoming AC current (i.e.,
utility power or a generator) to power your loads and to recharge the batteries. This inverter also
includes an extensive protection circuitry to shut down the inverter under certain fault conditions.
3.1 Inverter
Mode
When the MSH-RE Series is
fi
rst powered up, it defaults to the OFF mode.
The momentary ON/OFF
power switch (
Item 1, Figure 1-1) m
ust be lightly pressed to turn the inverter on. Subsequently
pressing this switch alternately turns the inverter off and on.
Inverter OFF
–
When the inverter is off,
no power is used from the batteries to power the AC
loads, and
the status
LED will be off. If AC power from an external source (utility grid or generator)
is connected and quali
fi
ed on the inverter’s AC input, this AC input power will pass through the
inverter to power the AC loads. However, if this AC power is lost, the AC loads will no longer be
powered because the inverter is off.
When the inverter is turned on, it operates either by “searching” or “inverting”, depending on the
connected AC loads.
Searching
– When the inverter is
fi
rst turned on, the automatic Search feature is enabled. This
feature is provided to conserve battery power when AC power is not required. In this mode, the
inverter pulses the AC output looking for an AC load (i.e., electrical appliance). Whenever an AC load
(greater than 5 watts) is turned on, the inverter recognizes the need for power and automatically
starts inverting. When there is no load (or less than 5 watts) detected, the inverter automatically
goes back into Search mode to minimize energy consumption from the battery bank. When the
inverter is searching, the inverter’s green LED
fl
ashes (fast).
Info:
The factory default value for the Search feature is 5 watts. It can be turned off
or adjusted from 5 to 50 watts using a remote display (ME-RC, ME-ARC, or ME-RTR).
Inverting
–
When a load greater than 5 watts is connected to the inverter output, the MSH-RE
Series inverts the DC power from the battery and supplies 120 VAC power to your sub-panel. The
inverter’s green LED
fl
ashes once every 2 seconds (medium
fl
ash) to indicate it is inverting. The
amount of time the inverter can be inverting and
providing power is directly related to the amount
of AC loads that are connected, and the capacity of the battery bank. Refer to Figure 3-1 to see
the
fl
ow of power (GRID and GEN) from the DC input to the AC output while in the Inverter mode.
NEUTRAL IN
AC GROUNDS
Power Transformer
FET Bridge
AC
DC
DC
IN
DC POSITIVE
DC NEGATIVE
AC
Output
Relay
NEUTRAL OUT
AC2 Hot
Transfer Relay
HOT OUT
GEN IN (AC2)
GRID IN (AC1)
INV
OUT
CB1
(60A)
AC1 Hot
Transfer Relay
120
VAC
CB2
(60A)
CB3
(60A)
Figure 3-1, Power Flow – Inverter Mode