Magnetrol Jupiter JM4 Safety Manual Download Page 9

ORI-652 Jupiter

®

 Model JM4 Magnetostrictive Transmitter – SIL Safety Manual

 

9

Step Action

1

Bypass the PLC or take other action to avoid a false trip.

2

Remove power from the Unit.  (This clears any potential soft RAM errors.)  Inspect the Unit in 

detail outside and inside for physical damage or evidence of environmental or process leaks.

a.) Inspect the exterior of the unit housing. If there is any evidence of physical damage that 

may impact the integrity of the housing and the environmental protection, the unit should 

be repaired or replaced.

b.) Inspect the interior of the Unit. Any evidence of moisture, from process or environment, is 

an indication of housing damage, and the unit should be repaired or replaced.

3

Restore power to the Unit. Use the Unit’s “DIAGNOSTICS” menu to observe “Present Status” 

and to review “EVENT HISTORY”.  Up to 10 events are stored.  The events will be date and 

time stamped if the internal clock is set and running.  It is suggested that the internal clock be 

set at the time of commissioning of the unit.  If the clock is set at the time of the proof test event 

times are calculated. 

a.) Observe the “Present Status”.  “Present Status” should be “OK”. 

b.) Review the “EVENT HISTORY”. 

i.)  Messages in the “EVENT HISTORY” must be investigated and understood. 

ii.)  Corrective actions should be taken for critical messages that indicate performance may 

be affected.

4

Use the Unit’s “DIAGNOSTICS” menu to perform a loop current test.  Choose the menu “DIAG-

NOSTIC/ADVANCE DIAGNOSTICS/TRANSMITTER TESTS/Analog Output Test” to change the 

output loop current and confirm the actual loop current matches the value chosen. 

a.) Send a HART command to the transmitter (or use the local user interface) to go to high 

alarm current output, 22mA, and verify that the analog current reaches that value.

i.)  This step tests for compliance voltage problems such as low supply voltage or increased 

wiring resistance. 

ii.)  This also tests for current loop control circuitry and adjustment problems.

b.) Send a HART command to the transmitter (or use the local user interface) to go to low 

alarm current output, 3.6mA, and verify that the analog current reaches that value.

i.)  This step tests for high quiescent current and supply voltage problems.

ii.)  This also tests for current loop control circuitry and adjustment problems.

c.)  Exit the “Analog Output Test” and confirm that the output returns to original state, with the 

proper loop current as indicated and controlled by the unit. 

Summary of Contents for Jupiter JM4

Page 1: ...oftware v1 x Magnetostrictive Level Transmitter This manual complements and is intended to be used with the Orion Instruments Jupiter Model JM4 Magnetostrictive Level Transmitter Installation and Oper...

Page 2: ...lation 6 5 3 Skill Level of Personnel 6 5 4 Necessary Tools 6 5 5 Configuration 6 5 5 1 General 6 5 5 2 Configuration 7 5 5 3 Write Protecting Locking 7 5 6 Site Acceptance Testing 7 5 7 Recording Res...

Page 3: ...section of the wire alloy This in turn creates a vibratory disturbance which begins to travel through the wire at a very constant rate of speed The disturbance is later detected via a sensing device...

Page 4: ...operly under the low alarm condition The only unsafe mode is when the unit is reading an incorrect level within the 4 20 mA range 2 deviation MAGNETROL defines a safe failure as one in which the 4 20...

Page 5: ...e Description Files is also required if HART is used Manufacturer Code 56 hex Model JM4 Device ID 56DF hex device revision 1 DD revision 1 For device installations in a classified area the relevant sa...

Page 6: ...NOTE This SIL evaluation has assumed that the customer will be able to acknowledge an over or undercurrent condition via the Logic Solver 5 3 Skill Level of Personnel Personnel following the procedure...

Page 7: ...9 999 NOTE Default Password 0 Password disabled Refer to the Model JM4 Installation and Operating Manual Bulletin ORI 650 for additional information on password pro tection It is required that after c...

Page 8: ...o maintain the appropriate Safety Integrity Level of a Safety Instrumented System it is imperative that the entire system be tested at regular time intervals shown as TI in the appropriate standards T...

Page 9: ...esent Status Present Status should be OK b Review the EVENT HISTORY i Messages in the EVENT HISTORY must be investigated and understood ii Corrective actions should be taken for critical messages that...

Page 10: ...have evidence of excessive noise iv If possible compare to Echo curve from commissioning to assure that performance has not changed significantly c Choose the menu DIAGNOSTICS ADVANCED DIAGNOSTICS IN...

Page 11: ...e manufacturer that the level transmitter Magnetostrictive 4 20 mA Model JM4 511x xxx is suitable for the use in safety instrumented systems according to IEC 61511 1 if the safety instructions and fol...

Page 12: ...12 ORI 652 Jupiter Model JM4 Magnetostrictive Transmitter SIL Safety Manual...

Page 13: ...IL 2 HFT 0 Single Float SFF 93 1 PFDavg 1 97E 03 Dual Float SFF 91 9 PFDavg 1 96E 03 Proof Test Interval Annually refer to PFD Graph below 7 4 PFD Graph The resulting PVDAVG Graph generated from the e...

Page 14: ...Lifetime of Critical Components According to section 7 4 9 5 of IEC 61508 2 a useful lifetime based on experience should be assumed Although a constant failure rate is assumed by probabilistic estima...

Page 15: ...Safety Related Systems ANSI ISA 84 00 01 2004 Part 1 IEC 61511 1Mod Func tional Safety Safety Instrumented Systems for the Process Indus try Sector Part 1 Hardware and Software Requirements ANSI ISA 8...

Page 16: ...ry inspection finds the cause of the claim to be covered under the warranty If the trouble is the result of conditions beyond our control or is NOT covered by the warranty there will be charges for la...

Reviews: